Screen Setup Menu 9300 Series User’s Guide
Page 34 Chapter 2 - Using The Front Panel

Display Mode

There are two display modes: PROGRAMMABLE MODE and FIXED MODE. The default
is programmable mode, which provides eight data display screens which can be
configured to meet your requirements (see “Custom Front Panel Displays”). Fixed
Mode dis pla ys f our scr een s, eac h wi th l arg e characters in the display, easily visible
from a distance. The four fixed mode screens display Average Volts, Average
Amps, kW total, and PF total. You cannot customize the fixed mode displays.
Screen Setup Menu
The SCREEN SETUP menu screen allows you to change the data displayed on the
eight display screens. From the SELECT SETUP menu, select SCREEN SETUP. The list
of display titles appear that correspond to each of the eight display screens (see
“Default Front Panel Display Screens”). The screen number with an asterix (*)
beside it indicates the active display (the screen displayed before you entered
SELECT SETUP). Select the screen you want to change, and press the round button.
Two settings appear, VALUES and STYLE, that allow you to specify which
measurements to display.

Style

The STYLE setting defines the number of parameters on each screen. This setting
has five options for each display screen: ONE PARAMETER, TWO PARAMETER, THREE
PARAMETER, FOUR PARAMETER, and DISABLED. Select the number of values you
want to display (the fewer values you select for display, the larger the
measurement will appear on the display screen).
If you select a large style (for example, one value) for a display screen that is
already set to display more than one value, the front panel warns you with a
message, and displays only the first value — the links to the undisplayable values
are severed and have to be reprogrammed.

Values

The VALUES setting specifies which of the device’s measurements are displayed on
each display screen. When you change the value displayed on a screen, you are
presented with a complete list of the meter’s measurements. Using the lists of
modules provided, select the values you want to have displayed on that display
screen.
The number of VALUES you can select is a function of the STYLE setting. You cannot
select more values than the style is set to display.
Style = One Parameter
Style = Four Parameter