9300 Series User’s Guide Data Logging Setup
Chapter 3 - Default Meter Functionality Page 47
Sag/Swell Logging (9350 only)
The meter logs the following output register values:
Changing the Frequency of Logging
The two Periodic Timer modules that control the frequency of different data
recording are as follows:
“EgyDmd Log” Trg controls the frequency of logging for the Energy and
Demand Log (this log is used for generating reports using Reporter).
“Hist Log Trg” controls the frequency of Historic Data logging.
Change the value in the Period setup register to change the frequency of data
logging (Period values are specified in seconds). Do not change the Sync Mode
setup register.
Changing the Log Depths
Change the value in the Depth setup register to increase the number of records
stored in the recorder. The RecordMode setup register controls how the Data
Recorder will overwrite old records; refer to the Data Recorder module description
in the online ION Programmer’s Reference before changing this setup register.
Changing Waveform Recording
The Waveform Recorder modules do not require changes to their default settings.
If you want to change the format of the recorded waveforms, refer to the
Waveform Recorder module description in the online ION Programmer’s Reference.
Changing the Parameters that are Logged
The meter’s factory configuration logs a comprehensive set of energy, power and
harmonics parameters. You cannot change which parameters are logged by
configuring a setup register. Adding or deleting a log’s parameters is an advanced
procedure, as it requires changes to the links between modules.
The software “Using Designer software” section of Using WinPM.Net describes
adding and deleting links between modules. Once you are comfortable editing
module links, change logged parameters by linking the output registers you want
logged to the inputs of an ION Data Recorder module.
Sag/Swell Log
SS1 DistDur SS1 DistV1Min
SS1 DistV1Max SS1 DistV2Min
SS1 DistV2Max SS1 DistV3Min
SS1 DistV3Max SS1 DistNominal