Standard I/O devices

The standard I/O devices such as process monitor, process operation keyboard, configuring keyboard, mini floppy disk unit, logging printer and message printer are described in Section 5.

The interface modules for operation channel generate the RGB signals for the process monitors. They also have three 20-mA current loop interfaces to which the process operation keyboard or the configuring keyboard and 2 printers (logging printer and message printer) are connected.

No operation channel interface modules are essential if the

AS 235 H is always operated and configured centrally. However, the use of an interface module is recommended for diagnostics. The operation channel interface modules must be ordered together with the standard devices.

In contrast to the AS 235 system, the process monitors, key- boards and printers in the AS 235 H are not directly connected to the operation channel interface module. The process motors are connected to the operation channel interface modules of the two partial systems via video relays. A video relay is assigned to each operation channel. The video relays ensure that the con- nected process monitors always display the same screen con- tents. The process monitors are connected to the active partial system when transferring to asynchronous operation. The video relays are also connected to the synchronization modules for this purpose.

The signal cables of the keyboards and printers are connected to the operation channel interface modules of the two partial sys- tems via distribution cables.

The keyboard and printer distributors as well as the video relays are components of the parts set for operation channel switch- over which belongs to the delivery of an operation channel.

An additional printer distributor is required if a second printer is to be connected to an operation channel, and must be ordered separately (option).

Possible connections and a summary of connecting cables: see page 3/29 ff.

The combinations which can be ordered for the standard I/O devices comprise:

• Interface module for operation channel 1

6DS1 330-8CA

(with redundant basic unit: 2 off)

 

• PBT 65 process operation keyboard 1)

6DS3 305-8BA

• Configuring keyboard

6DS3 303-8AA

with connecting cable, 1 m

6DS8 102-8AC

Mini floppy disk unit with connecting cables for 6DS3 900-8AE signal transmission and power supply, 3 m each

• Parts set for operation channel switchover

C79165-A3012-D70

• In addition for operation channel 2:

 

– Interface module for operation channel 2

6DS1 330-8CA

(with redundant basic unit: 2 off)

 

– Second PBT 65 process operation keyboard

6DS3 305-8BA

– Parts set for operation channel switchover

C79165-A3012-D70

• One process monitor per operation channel as option:

– Process monitor SCM 2140-I 2)

6GF6100-1BV

Extension units

Depending on the complexity of the automation function, the capacity of the AS 235 H can be increased up to max. 91 slots for I/O modules by the addition of up to 7 extension units.

The extension units EE1 to EE3 are connected to the basic unit via 2 separate, redundant I/O buses 1 (A). Each of these buses is connected to the CPU of an AS 235 H partial system via a sep- arate interface module for I/O bus 1 (A). These extension units are fitted in the basic cabinet.

1)Order connecting cables for signal transmission and power supply in addition, see page 5/5 (process operation keyboard)

2)Order connecting cables for signal transmission in addition, see page 5/4 (process monitor)

Automation systems

AS 235 H

Basic cabinet

Extension units EE4 to EE7 are fitted in the extension cabinet. These are also connected to the CPU of an AS 235 H partial sys- tem via 2 separate I/O buses 2 (B) which are redundant to one another, each of which has its own interface module for

I/O bus 2 (B).

An extension unit of the AS 235 H automation system consists of a subrack with slots for 13 I/O modules, I/O bus comparator and switchover module, and a DC 5 V power supply module.

When ordering the extension units it is possible to select whether the extension unit EE1 is to be delivered on its own, together with EE2, or together with EE2 and EE3.

The following components are supplied:

• 1, 2 or 3 subracks

 

with slots for 13 I/O modules

 

– For wire-wrap system

6DS9 002-8BB

– For Maxi-Termi-Point system

6DS9 002-8BA

• 1, 2 or 3 cable ducts, 2 U high

6DS9 906-8AB

• 1, 2 or 3 covers, 2 U high

6DS9 906-8BB

• Cable set for power supply

 

– For EE1

6DS9 908-8GB

– For EE2

6DS9 908-8GC

– For EE3

6DS9 908-8GD

• Cable set for I/O bus, + 5 V, 0 V

 

– With EE1 on its own

6DS9 911-8GA

– With EE1 and EE2

6DS9 911-8GB

– With EE1, EE2 and EE3

6DS9 911-8GC

• 1, 2 or 3 I/O bus comparator and

6DS1 144-8AA

switchover modules

 

• 1, 2 or 3 upgrading sets with

C79451-A3117-D29

switched-mode regulator DC 5 V (6DS1 006-8AA)

The extension units are supplied directly with DC 24 V from the power supply subrack. Each extension unit is fused separately with 16 A on the power supply subrack. The DC 5 V supply is taken from the power supply module DC 5 V.

In addition to the I/O modules, the interface module for 20-mA local bus N-V.24 can be inserted into the I/O slots of the

AS 235 H system. One interface module N-V.24 can be inserted per interface module.

Accessories for the extension units: see Ordering data “Further options for AS 235 H basic cabinet”.

I/O modules

The I/O modules are the process interface of the AS 235 H auto- mation system. They comprise signal modules and function modules, including calculation modules. See Section 4 for the properties, functions and Ordering data of the I/O modules.

Up to 13 I/O modules can be inserted into each of the extension units (max. 3) of the basic unit. Please observe the max. thermal loading (see standard cabinets and accessories, page 3/23).

A further 52 I/O modules can be inserted into an additional extension cabinet with up to 4 extension units, thus enabling a total of 91 I/O modules per AS 235 H system.

One ES 100 K extension system can additionally be connected per I/O bus 1.

During planning it should be noted that the 16 A with which each extension unit is fused must not be exceeded.

The I/O modules can be supplied coded, inserted and with labelled slots. Arrangement, designation and connection dia- grams (including address data) are required from the orderer.

• Coding, inserting and labelling

6DS5 705-8AA

for 1 I/O module

 

Siemens PLT 111 · 1999

3/11

Page 35