Bus communication

Design

Connection distributor AV

 

N-AS

 

 

 

 

 

 

 

 

 

 

 

6DS9

201-8CA or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6DS8

204-8.. (without AV)

 

 

 

 

6DS8 201-8..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AF

AF

AV

 

 

 

UI

UI

Remote bus A

 

 

 

Remote bus B

or

N-AS N-AS

6DS9 201-8CA + 6DS8 201-8.. or

6DS9 201-8FC

with 5 plugs

The connection distributor AV (Order No. 6DS9 207-8AA) has a vacant plug connection to the redundant 20-m local bus for the connection of configuring aids (e.g. personal computer with the PROGRAF AS+ engineering tool). It must be connected to the local bus via a cable for this purpose.

Bus converter Ul

A bus converter is required to connect individual participants or a local bus with several participants to a remote bus. It performs continuous signal conversion between the local bus and the remote bus or vice versa without intermediate storage. The cou- pling is inductive and non-reactive.

Possible locations:

AS 235 and AS 235 H basic cabinet

AS 235 K basic system

Remote bus connection unit

Bus coupler

Fig. 6/6 Connection of a redundant remote bus (AS 235 / AS 235 K/ AS 235 H)

Redundant remote bus

2 bus converters UI are required to connect an automation sys- tem to a redundant remote bus. The bus converters are con- nected

in the AS 235 system via a cable 6DS9 201-8CA to the N-AS and the connection distributor AV,

in the AS 235 H system via a cable 6DS9 201-8FC to both N-AS and the connection distributor AV, and

in the AS 235 K system via a cable 6DS8 204-8MB to the N-AS.

• Remote bus connection subrack.

See Catalog PLT 130 for detailed information on the bus con- verter.

Connector board AF "Remote bus"

The remote bus cable is connected to the bus converter via the connector board AF "Remote bus". The board is provided with a terminating resistor which can be activated using a jumper. The resistor is activated in the first and last bus participants.

When converting/retrofitting, cable combinations together with the cable 6DS8 201-8.. are possible instead of the above cables (cf. Fig. 6/6).

Local bus interface modules

Interface module for

For connection of the following systems and

20-m local bus

devices to the CS 275 plant bus

Type

 

N-AS

AS 235 and AS 235 K automation systems

6DS1 223-8AC

 

N-AS

AS 235 H automation system

6DS1 223-8AA

 

e.g. TELEPERM M cabinet with

AS 235 H

UI UI

AF

AF

a

a

e.g. remote bus connection unit (OS 525)

UI

UI

AF

AF

e.g. TELEPERM M cabinet

UI

UI

AF

AF

a

a

N-BK

Bus coupler

6DS1 223-8AB

 

 

 

N-AT

OS 525 / WinCC/TM-OS operator systems,

6DS1 222-1AB10/20

AT-compatible personal computers,

 

SIMATIC PC and PG programming devices

N-V.24

Computers from other manufacturers via V.24

6DS1 202-1AB

or 20-mA current loop interface

 

 

N-S5 1)

SIMATIC S5-155U programmable controllers

6DS1 206-8AA

 

 

 

1) Discontinued product

Further information on the various interface modules can be found in Catalog PLT 130 and the following manuals:

• CS 275 bus system

C79000-G8076-C6

N-V.24 coupling of computers from

 

other manufacturers

C79000-G8076-C87

KSN-S55 / S5-155U programmable controller C79000-G8076-C319

Remote bus A Remote bus B

a Terminating resistor F (activated by jumper)

Fig. 6/7 Redundant remote bus with terminating resistors

Overvoltage protection

The participants connected to the remote bus can be exten- sively protected against destruction by overvoltages by means of the coarse and fine overvoltage protection units.

The coarse protection limits high-voltage signals of high power to the arc voltage. The coarse protection is able to handle brief peaks in the kA range. It is installed where the remote bus enters the building. The fine protection reduces the residual voltage which passes the coarse protection down to a value between the internal conductor and the screen of the remote bus cable which is harmless for the amplifier of the inductive coupler in the bus converter. The fine protection is fitted on the connector AF.

6/4