AS 235 automation system
The AS 235 automation system is the cabinet version of the |
range. It can be ordered in the form of two ordering units: basic |
cabinet and extension cabinet: |
The basic cabinet is the main component of the AS 235 automa- |
tion system. It contains all components required for the AS 235 |
system to function. It can therefore also be used on its own, i.e. |
without an extension cabinet. |
The extension cabinet increases the number of slots for I/O mod- |
ules. It can only be operated in conjunction with the basic cabi- |
net with up to 3 extension units. When using an extension cabi- |
Automation systems
AS 235
Basic cabinet
Communication
via CS 275 plant bus
GE |
| M |
SV | SV | |
|
| L |
6 I/O | ZE |
modules |
| net it is possible to increase the number of slots for I/O modules | |
| in the basic cabinet (48) up to a maximum of 90. | |
|
|
|
Basic cabinet |
| |
The basic cabinet consists of the following main components: | ||
Basic unit |
| |
The basic unit of the AS 235 automation system consists of: | ||
• Subrack |
| |
– For | 6DS9 | |
– For | 6DS9 | |
• Power supply subrack with |
| |
– Slots for power supply and |
| |
logic modules and |
| |
– 6 slots for I/O modules |
| |
• Power supply module |
| |
– DC 24 V / DC 24 V | ||
– DC 24 V / DC 5 V | ||
• Alarm logic module | 6DS1 | |
• Central processing unit with |
|
– Central processor module | 6DS1 | |
– EDC memory module 4000 Kbyte | 6DS1 |
I/O bus |
|
EE |
|
14 I/O | MO |
modules | (max. 6) |
DR | Printer |
|
|
|
|
|
PBT, ST |
|
| ||||
EE | Extension unit |
|
|
|
|
|
GE | Basic unit |
|
|
|
|
|
ML | Alarm logic module |
|
|
|
|
|
MO | Monitor |
|
|
|
|
|
PBT | Process operation keyboard DR |
|
|
| ||
ST | Configuring keyboard |
|
|
|
|
|
SV | Power supply module |
|
|
|
|
|
UI | Bus converter |
|
|
|
|
|
ZE | Central unit |
|
|
|
|
|
MO |
– Backup battery for memory module | |
– AS 235 system software, version G | 6DS5 |
– Interface module for I/O bus 1 | 6DS1 |
• Interface module for mini floppy disk unit | 6DS1 |
• Interface module for operation channel 1 | 6DS1 |
• Bus terminator module | |
• Cable duct, 2 U high | 6DS9 |
• Cover with wiring duct | 6DS9 |
• Cable set for power supply and alarms | 6DS9 |
Fig. 3/2 AS 235 automation system, system configuration
The alarm logic modules monitor the voltages L+, PM (DC 24 V each) and +5 V as well as the I & C signals for overtemperature, door contacts, fan contacts and spare contacts, and trigger the current lamps.
The central processor is especially tailored to the processing of
The subrack for the basic unit of the AS 235 system corresponds to the ES 902 system and is 10 U high. It is the supporting sys- tem for the other components of the basic unit, the interface modules for the local bus, and the I/O modules. The process sig- nal lines for the 6 I/O modules are connected to the rear, the plug connectors are equipped with
If the process signal cables leading to I/O slot 6 are to the con- nected in the cabinets also using the
The power supply module
The basic unit is equipped with 1 or 2 alarm logic modules depending on the configuration of the automation system. The alarm logic module ML1 is assigned to the basic cabinet. The alarm logic module ML2 is only required if the AS 235 system consists of a basic cabinet and an extension cabinet and has a basic unit with
•the
•the
•the transfer memories of the interface modules for I/O bus, operation channel, mini floppy disk unit and local bus.
The memory module with Error Detection and Correction EDC can correct a
The interface module for I/O bus establishes the connection between the
•The interface module for I/O bus 1 (A) supplies the I/O modules plugged into slots 1 to 5 of the basic unit and the 3 extension units of the basic cabinet. It is always required, and belongs to the standard delivery of the basic unit.
•The interface module for I/O bus 2 (B) must the ordered as an option. It connects slot 6 for I/O modules in the basic unit and the 3 extension units of the extension cabinet to the central pro- cessing unit via I/O bus 2 (B). It is therefore only required if slot 6 in the basic unit is to be used, or if an extension cabinet is used in addition to the basic cabinet.
Siemens PLT 111 · 1999 | 3/3 |