Coupling with other systems

SIMATIC S5 I/Os / ET 100U

Interface module for ET 100U

Interface module for ET 100U

￿The interface module for ET 100U, 6DS1 327-8AA, is a double- height compact subassembly. The front panel width is 30.48 mm (2 standard slots).

The module has 2 base plugs for the I/O bus interface and the power supply, as well as a front plug (4-contact male connector) with screw terminals for lines 1 and 2.

ET 100U electronic terminators, ER 701-2 and ER 701-3 expan- sion racks and EU 183U, EU 185U and EU 186U expansion units can be connected to each line in any order. The total cable length up to the last device must not exceed 3000 m.

The front panel of the interface module has a slot for inserting a configuration EPROM submodule. This is required when con- necting ET 100U electronic terminators.

Mode of operation

Up to 3 interface modules 6DS1 327-8AA can be inserted into any I/O bus slots in an AS 235 automation system. Each module occupies several module numbers.

The interface modules adapt the I/O bus interface to the serial SIMATIC S5 interface. In this manner, analog and digital input/ output modules of the ET 100U electronic terminator or the S5-115U, S5-135U and S5-155U programmable controllers can be connected to an AS 235 automation system.

If SIMATIC analog input modules are used, linearization of the characteristic and compensation of the cold junction tempera- ture must be carried out by the user for non-linear transmitters and thermocouples.

Following application of the supply voltage after briefly switching off the mode switch on the module and following elimination of an interruption in the transmission cable on one of the two lines, the interface module carries out a configuration operation in which it stores an image of the connected SIMATIC S5 periph- eral devices and used I/O modules in its main memory.

The configuration data for the connected SIMATIC S5 expansion units are determined by reading the configuration lists in the expansion units, and for the ET 100U electronic terminator by scanning the configuration EPROM submodule generated by the user. The configuration data are the reference data for the interface module.

The AS 235 automation system communicates with the

SIMATIC S5 peripheral devices via an intermediate memory on the interface module. Both the automation system and the pro- cessor of the interface module store transfer data in this mem- ory.

The processor of the interface module cyclically processes the connected SIMATIC S5 I/O modules, transfers the output data entered by the automation system to the SIMATIC S5 output modules and updates the input area in the intermediate memory by scanning the SIMATIC S5 input modules.

Data transfer between the interface module and the SIMATIC S5 peripheral devices is carried out in half-duplex operation. The initiative always originates in the interface module.

The data are protected by 1 or 2 test bytes depending on the set transmission rate (cyclic BGH code).

If a plug on any SIMATIC S5 device is disconnected, the trans- mission line to the other devices is not interrupted (party line).

Technical data

￿

 

 

L+

DC 24 V, 500 mA

 

Power supply

 

 

PM

DC 24 V, 35 mA

 

Number of channels/interfaces

2, operated in parallel

 

Interface to

 

 

 

– ET 100U, ER 701-2, EU 183U,

Asynchronous, half-duplex,

 

EU 185U and EU 186U

 

similar to RS 485 I/O standard

 

– TELEPERM M

 

I/O bus (TTL)

 

Connectable devices per interface

Max. 32 SIMATIC S5 devices, can

 

line (channel)

 

be mixed as required;

 

 

 

2 x number of ET 100U + number

 

 

 

of expansion units 32

 

Configuration per AS 235 automa-

Max. 3 interface modules

 

tion system

 

 

 

Transmission rate

 

375 / 187.5 / 62.5 / 31.25 kbits/s,

 

 

 

adjustable

 

Max. line length

 

 

 

 

 

 

– With 375 kbits/s

 

0.5 km

 

– With 187.5 kbits/s

 

1 km

 

– With 62.5 kbits/s

 

1 km

 

– With 31.25 kbits/s

 

3 km

 

Transmission cable

 

Screened, twisted in pairs,

 

 

 

0.5 to 1.5 mm², flexible

 

Permissible ambient temperature

 

 

– Operation

 

0 to +55 °C

 

– Transport and storage

 

-40 to +70 °C

 

Weight

 

Approx. 0.5 kg

 

 

 

 

Ordering data

 

 

 

Interface module for ET 100U

6DS1 327-8AA

IM 318-3 interface module

6ES5 318-3UA11

for EU 183U, EU 185U, EU 186U

 

expansion units and ER 701-2 or

 

ER 701-3 subracks

 

Adapter casing

6ES5 491-0LB11

for ER 701 subrack

 

IM 318-8 interface module

6ES5 318-8MA12

for ET 100M electronic terminator

 

EPROM memory submodule

6ES5 376-1AA11

376

 

for generation of configuration

 

￿EPROM for ET 100U connection

 

COM ET 100U parameterization

 

software

 

– On 3.5" diskette

6ES5 835-3SC12

– On 5.25" diskette

6ES5 895-3SC12

SIMATIC S5 I/O modules,

See Catalog ST 50

ET 100U electronic terminator

 

Instruction Manual for interface

 

module 6DS1 327-8AA

 

– German

C79000-B8000-C231

– English

C79000-B8076-C231

 

 

 

￿