This catalog is out of date, see note on page 1

TELEPERM M

Introduction

System data

General system data 1)

￿

 

 

Permissible ambient temperature

 

 

• Modules

0 to 70 °C

 

– Operation

 

Δt/h

Max. 10 K

 

Δt/min

Max. 0,5 K

 

– Transport and storage

-40 to +70 °C

• Cabinet (operation)

 

 

Cabinet ambient temperature at

 

 

1 m above cabinet base

0 to 40 °C

 

Reduction in specified temperature

10 K/1000 m

 

above 1000 m above sea level

 

 

Permissible humidity

Operation

Storage

– Annual average

Max. 75 %

Max. 65 %

– On 30 days/year

Max. 95 %

– On 60 days/year

Max. 85 %

Condensation not permissible

 

 

Mechanical ambient conditions

 

 

Operation stress

 

 

 

 

(modules in subrack)

 

 

– 10 to 60 Hz

0.15 mm deflection

– 60 to 500 Hz

2 g acceleration

System cabinet

 

 

– 10 to 58 Hz

0.035 mm deflection

– 58 to 500 Hz

0.5 g acceleration

Transport stress

 

 

 

 

(modules in subrack)

 

 

– 5 to 8 Hz

7.5 mm deflection

– 8 to 500 Hz

2 g acceleration

Design, earthing conditions

 

 

Potential difference between all

Max. 7 V

 

ground star points of distributed

 

 

systems

 

 

Insulation

According to VDE 0160

Protection class

Class l

 

Insulation of modules, clearances and

According to VDE 0110

creepage distances from pin to pin or

 

 

from conductor to conductor

 

 

Signal data

 

 

(interface to field level)

 

 

• Binary signals

 

 

DC voltage

Referred to M potential

Signal definition

 

 

Inputs

Outputs

– L (low)

-30 to +4.5 V

0 to 2.5 V

– H (high)

+13 to +33 V

L+ to

 

 

(L+ - 2.5 V)

Input currents

 

 

– Electronic transmitters

0.5 mA

Typical values for

– Contacts

4 mA

configuring

Output currents with DC 24 V

8.5 mA/100 mA/120 mA

Power signals

Max. 400 mA

Binary signal outputs

Short-circuit-proof and

 

overload-proof

 

 

 

General system data

￿

• Analog signals

 

DC voltage

Referred to MZ

– Rated range of use

-10 to +10 V

 

-10 to 0 V

 

0 to +10 V

– Overflow range

 

-10.5 to +10.5 V

– Input resistance

100 kΩ

– Output loading capacity

1 mA

Direct current

Referred to M

– Rated range of use

0 to 20 mA or 4 to 20 mA

– Overflow range

0 to 21 mA or 3.7 to 21 mA

– Input resistance

12.5, 50 or 350 Ω

– Rated output load

500 or 600 Ω

Analog signal outputs

 

Short-circuit-proof and over-

 

load-proof

 

Overvoltage resistance of binary and

Class II

 

analog inputs and outputs according

 

 

to IEC information 255-4 (Fig. 1/2)

 

 

 

 

Fig. 1/2 Overvoltage resistance / dynamic destruction limit

1)Deviations possible in individual cases. Refer to technical data of individ- ual components

1/4

Siemens PLT 111 · 1999

Page 4
Image 4
Siemens AS 235 appendix System data, General system data