Siemens AS 235 appendix Standard cabinets IP 20 without heat exchanger, Design, Technical data

Models: AS 235

1 90
Download 90 pages 58.99 Kb
Page 50
Image 50
Siemens PLT 111 · 1999

This catalog is out of date, see note on page 1

Automation systems

Standard cabinets

Standard cabinets IP 20 without heat exchanger

2,3

1

15

14

14

14

12

11

11

4

13

 

The cable bars are included in the standard delivery of the cab-

 

inet. The locations for installation of the video relays and the con-

 

nector boards for remote bus are identified accordingly.

 

The standard cabinets with degree of protection IP 20 are

 

equipped with:

 

• Main frame with conductive, corrosion-proof surface; fitted off-

5

set to one side and electrically connected to the cabinet frame.

 

Side members of the main frame with fixing holes for mounting

 

the subracks

 

Three-part metal cable duct with cover plate on the right-hand

 

side member on the cable connection side for the ribbon

 

cables of the I/O bus, for power supply cables, internal bus

 

connections and cables to the operation devices

 

• Cable duct 80 mm x 75 mm on the left-hand side member for

 

internal wiring of process signals

 

• Cabinet connection element support for up to 90 32-way cabi-

 

net connection elements (SAE)

 

• Screen bars for connection of process cable screens

 

• Cable clamping rails for the process cables

 

• Screen board on the right-hand side of the cabinet for external

 

operation and monitoring devices

 

• Screen board on the right-hand side of the cabinet for remote

 

bus cables

 

• Socket for connection of a telephone to the internal telephone

6

network. The socket is not wired-up and is accessible from the

 

front of the cabinet. It consists of a two-pin plug connector 4/13

 

DIN 47 284 with insulated sleeve and cover

7

• 4 door contacts with associated cable set

6

• Bar for 24-V terminals

8

• 2 thermostats for overtemperature detection.

9 10

1Cabinet housing

2Cabinet alarm lamp

3 Lamp test pushbutton

4 Socket for telephone connection

5 Slots for video relay (AS 235 H basic cabinet only)

6 Slots for connector boards AF "Remote bus" (basic cabinet only) 7 Screen bar for connecting bus cable screens

8 Screen board

9 Three-part cable duct

10 Cable duct

11 Screen bar for connecting process cable screens

12 Bar for 24 V terminals

13 Main frame

14 Bar for fixing the cables

15 Cabinet connection element support

Fig. 3/11 Standard cabinet without heat exchanger

Standard cabinet with degree of protection IP 20, ￿without heat exchanger

Design

Cabinet with two-leaf doors at front and rear; lift-off doors. Each door with 3 rows of ventilation slots.

Front and rear of cabinet each with a top bezel panel with cabi- net alarm lamp and lamp test pushbutton.

The cables are connected to cable bars in the rows of holes in the cabinet frame using commercially available parts.

3/26

Technical data

￿

 

 

 

 

 

Door width

450 mm each

 

 

 

Angle of opening of doors

 

 

 

 

 

– Separate cabinet

180°

 

 

 

 

– Cabinet row

135°

 

 

 

 

Degree of protection to DIN 40050

 

 

 

 

 

– Cabinet 6DS9 300-8AA (400 mm)

IP 20

 

 

 

 

– Cabinet 6DS9 302-8AA (600 mm)

IP 20

 

 

 

 

Permissible cabinet inlet temperature

25 °C

30°C

35°C

40°C

 

Permissible thermal load Ps max

450 W

420 W

380 W

350 W

– with fan subassembly

700 W

 

 

 

 

Permis. humidity (no condensation)

65%

 

 

 

 

– Operation

 

 

 

 

– Transport and storage

75%

 

 

 

 

Cabinet colors

Acrylic resin fine-texture single-

 

– Cladding

coat lacquer

 

 

 

Light beige (Siemens color 103)

 

– Cabinet frame

Gray-brown (Siemens color 105)

 

– Labelling strips

Ochre (Siemens color 100)

 

Required floor loading capacity

1000 kg/m²

 

 

 

including weight of cables and traffic

 

 

 

 

 

Dimensions (H x W x D) in mm

 

 

 

 

 

– Cabinet 6DS9 300-8AA

2200 x 900 x 400

 

 

– Cabinet 6DS9 302-8AA

2200 x 900 x 600

 

 

Weight of empty cabinet

Approx. 130 kg

 

 

 

Option

 

 

 

 

 

Fan subassembly

 

 

 

 

 

 

 

 

 

 

– Supply voltage

DC 24 V

 

 

 

– Power consumption

Approx. 36 W

 

 

 

 

 

 

 

 

Page 50
Image 50
Siemens AS 235 appendix Standard cabinets IP 20 without heat exchanger, Design, Technical data