4 Creating Project Files—PLC to Devices

4Creating Project Files—PLC to Devices

This chapter covers configuration of the DTU3005 for PLC communications with Siemens devices. Once you have cre- ated a PLC to Devices project (see Chapter 3), follow the directions in this chapter to configure the project file. Then see Chapter 7 for directions on downloading the project to the DTU3005. See also Appendix D for wiring diagrams for your particular PLC, as required.

4.1Application Description

The PLC to Devices application allows a PLC to control and monitor up to 32 SEAbus devices or Siemens protective relays. In this application, the DTU3005B initiates all com- munications with both the PLC and the Siemens devices.

The DTU3005B uses an internal transfer table to transfer data to the PLC. The transfer table contains a block of selected real-time data parameters obtained from a device. The DTU3005B unit acts as a master to the PLC, and con- tinuously transfers the table data to the selected block of registers on the PLC. A delay option is provided for each device’s table entry to prevent unnecessarily slowing down

the scan time of the PLC as well as to give some device data transfers higher priority than others.

No ladder logic is required on the PLC to use the basic fea- ture of this application, which allows a limited amount of information to be transferred between the PLC and the devices. Ladder logic programming is required to use the command block function. The command block is used to send commands to the devices, such as operating or releasing relays, or resetting energy counters. See Section 4.11 for information on configuring this feature on the DTU3005B. The format of the command registers for each device are described in Appendix E.

The DTU3005B can automatically update diagnostic infor- mation in the PLC. It allows the PLC to determine when a device is not communicating. See Section 4.10 for informa- tion on enabling and configuring this feature. The format and content of the diagnostic registers are described in detail in Appendix F.

4.2Configuring the Project File

Once you have created or opened the project file, select Edit from the main menu to display the following menu items:

Port 1 (PLC)—allows you to select the model and con- figure the communications settings for the PLC con- nected to port 1.

Port 2 (Devices)—allows you to configure communi- cations settings for SEAbus devices or Siemens Pro- tective relays connected to port 2.

Port 3 (Passthrough)—allows you to select whether port 3 is used as a passthrough to the devices or the PLC.

Diagnostics—allows you to indicate if you want the DTU3005 to write communications diagnostic informa- tion to the PLC.

12

Siemens Energy & Automation, Inc.

Page 16
Image 16
Siemens DTU3005-B manual Creating Project Files-PLC to Devices, Application Description, Configuring the Project File