4 Creating Project Files—PLC to Devices

The relevant status codes (Text #) are listed below.

Table 4.1 7SJ600 Relay Information

For Requesting Status of the 7SJ600 Relay’s Three Binary Inputs

Text Number/Status Code

Description of Returned Binary

 

Suggested Value (Using This Conversion Table)

 

 

(default value returned if

Input Status Codes: I1

 

 

 

 

 

 

 

 

 

 

Inputs

I3

I2

I1

 

 

not converted)

indicates Input 1; I2,3 indicates

Value

 

 

 

 

 

 

 

 

 

 

 

Inputs 2 and 3

 

 

 

 

 

 

 

 

 

0

 

0

0

0

0

 

 

1342

I1,2 Inactive : I3 Active

4

 

0

1

0

0

 

 

1343

I1,3 Inactive : I2 Active

2

 

0

0

1

0

 

 

1344

I1 Inactive : I2,3 Active

6

 

0

1

1

0

 

 

1345

I2,3 Inactive : I1 Active

1

 

0

0

0

1

 

 

1346

I2 Inactive : I1,3 Active

5

 

0

1

0

1

 

 

1347

I3 Inactive : I1,2 Active

3

 

0

0

1

1

 

 

1348

I1,2,3 Active

7

 

0

1

1

1

 

 

For Requesting Status of the 7SJ600 Relay’s Two Trip Contacts and Two Signal Contacts

 

 

 

 

 

 

 

 

 

 

Text Number/Status Code

Description of Returned Trip

 

Suggested Value (Using This Conversion Table)

 

 

(default value returned if

and Signal Relay Status

 

 

 

 

 

 

 

 

 

 

Outputs

S2

S1

T2

T1

 

not converted)

Codes: S1,2 indicates Signal

Value

 

 

 

 

 

 

 

 

 

 

Relays 1 and 2; T1,2 indicates

 

Bits 15 . . . 4

3

2

1

0

 

 

 

 

 

 

Trip Relays 1 and 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1349

S1,2 T1,2 Open

0

 

0

0

0

0

0

 

 

 

 

 

 

 

 

 

 

 

1350

S1,2 T1 Open : T2 Closed

2

 

0

0

0

1

0

 

 

 

 

 

 

 

 

 

 

 

1351

S1,2 T2 open : T1 Closed

1

 

0

0

0

0

1

 

 

 

 

 

 

 

 

 

 

 

1352

S1,2 Open : T1,2 Closed

3

 

0

0

0

1

1

 

 

 

 

 

 

 

 

 

 

 

1353

S1 T1,2 Open : S2 Closed

8

 

0

1

0

0

0

 

 

 

 

 

 

 

 

 

 

 

1354

S1 T1 Open : S2 T2 Closed

10

 

0

1

0

1

0

 

 

 

 

 

 

 

 

 

 

 

1355

S1 T2 Open : S2 T1 Closed

9

 

0

1

0

0

1

 

 

 

 

 

 

 

 

 

 

 

1356

S1 Open : S2 T1,2 Closed

11

 

0

1

0

1

1

 

 

 

 

 

 

 

 

 

 

 

1357

S2 T1,2 Open : S1 Closed

4

 

0

0

1

0

0

 

 

 

 

 

 

 

 

 

 

 

1358

S2 T1 Open : S1 T2 Closed

6

 

0

0

1

1

0

 

 

 

 

 

 

 

 

 

 

 

1359

S2 T2 Open : S1 T1 Closed

5

 

0

0

1

0

1

 

 

 

 

 

 

 

 

 

 

 

1360

S2 Open : S1 T1,2 Closed

7

 

0

0

1

1

1

 

 

 

 

 

 

 

 

 

 

 

1361

T1,2 Open : S1,2 Closed

12

 

0

1

1

0

0

 

 

 

 

 

 

 

 

 

 

 

1362

T1 Open : S1,2 T2 Closed

14

 

0

1

1

1

0

 

 

 

 

 

 

 

 

 

 

 

1363

T2 Open : S1,2 T1 Closed

13

 

0

1

1

0

1

 

 

 

 

 

 

 

 

 

 

 

1364

S1,2 T1,2 Closed

15

 

0

1

1

1

1

 

 

 

 

 

 

 

 

 

 

For Requesting Status of the 7SJ600 Relay’s Four Programmable LEDs

 

 

 

 

 

 

 

 

 

 

 

 

Text Number/Status Code

Description of Returned LED

 

Suggested Value (Using This Conversion Table)

 

 

(default value returned if

Status Codes: L1,2 indicates

 

 

 

 

 

 

 

 

 

 

Outputs

L4

L3

L2

L1

 

not converted)

LEDs 1 and 2

Value

 

 

 

 

 

 

 

 

 

 

 

 

Bits 15 . . . 4

3

2

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1365

L1,2,3,4 Off

0

 

0

0

0

0

0

 

 

 

 

 

 

 

 

 

 

 

1366

L4 On : L1,2,3 Off

8

 

0

1

0

0

0

 

 

 

 

 

 

 

 

 

 

 

1367

L3 On : L1,2,4 Off

4

 

0

0

1

0

0

 

 

 

 

 

 

 

 

 

 

 

1368

L3,4 On : L1,2 Off

12

 

0

1

1

0

0

 

 

 

 

 

 

 

 

 

 

 

1369

L2 On : L1,3,4 Off

2

 

0

0

0

1

0

 

 

 

 

 

 

 

 

 

 

 

1370

L2,4 On : L1,3 Off

10

 

0

1

0

1

0

 

 

 

 

 

 

 

 

 

 

 

1371

L2,3 On : L1,4 Off

6

 

0

0

1

1

0

 

 

 

 

 

 

 

 

 

 

 

24

Siemens Energy & Automation, Inc.

Page 28
Image 28
Siemens DTU3005-B manual Description of Returned Trip