Siemens DTU3005-B manual Creating Project Files-Modbus Master to Devices

Models: DTU3005-B

1 54
Download 54 pages 7.78 Kb
Page 40
Image 40

5 Creating Project Files—Modbus Master to Devices

3.Select the device from the list by pressing Enter or the spacebar. The highlight moves to the Address field, and the PLC register fields now dis- play as shown in the example screen below.

4.With the Address field highlighted, enter the device’s address. This number should be between 1 and 254, and match the number programmed into the device itself. Press the Tab key twice to go to the Real-Time Data Registers field.

5.Enter the beginning register number in the Real- Time Data Registers field. Refer to Appendix A for valid register numbers for your PLC application. The DTU3005 Editor software supplies the last

register number after you enter the first. In the example above, the 4700 Power Meter uses 41 registers for its data. When you enter 1 for the first register, the last register becomes 42. If you

36

Siemens Energy & Automation, Inc.

Page 40
Image 40
Siemens DTU3005-B manual Creating Project Files-Modbus Master to Devices