3 Operating the SAMMS-MV Device
Function
Number
Function Description Range Step Size Default Value
F0 Select ambient temperature. 0 - 70º C 5º C 40º C
F1 Display (or change for SAMMS-MVE)
the control circuit number,
Enable/disable incomplete sequence
status.
0 - 9999 1 N/A
F2 Display the size for single-speed
controller, or the high-speed size for
two-speed motor controllers.
H3A, H3B, H3C, H6 As shown N/A
F3 Display the low-speed size for
two-speed controller. F3 is OFF for
single-speed motor controllers.
H3A, H3B, H3C, H6 As shown N/A
F4 Select the full-load current setting (I )
for the size for single-speed motor
controller or the high-speed size for
two-speed motor controllers.
H3A: 18 - 72A
H3B: 60 - 240A
H3C: 192 - 400A
H6: 320 - 720A
1A
1A
1A
2A
18
60
192
320
F4A Display the primary current if 5A
secondary CT's are used.
Function of size in F2 Function of size in F2 OFF (denotes
SAMMS sensors
in use)
F5 Select the full-load current setting (I )
for the low-speed size for two-speed
motor controllers. F5 is OFF for single
speed motor controllers.
H3A: 18 - 72A
H3B: 60 - 240A
H3C: 192 - 400A
H6: 320 - 720A
1A
1A
1A
1A
18
60
192
320
F5A Display the primary current if 5A
secondary CT's are used.
Function of size in F3 Function of size in F3 OFF (denotes
SAMMS sensors
in use)
F6 Select the service factor. 1 or 1.15 N/A 1.15
F6A Select type of motor. ODP or EFC N/A ODP
F7 Select the overload trip class. 2-23 1 10
F7A Select cold stall time. 5-100 1 10 (ODP) /
20 (EFC)
F8 Enable/disable autoreset of overload
and external trips.
ON/OFF N/A OFF
F9 Enable/disable phase unbalance
protection.
ON/OFF N/A ON
F10 Display the time to wait until the motor
can be restarted. Applies after an
overload trip with the winding, housing,
or rotor temperature above the
maximum allowed for restarting.
Real Time Value 1s N/A
F11 Enable/disable the emergency restart
capability.
ON/OFF N/A OFF
Table 3.8 Motor control and protection functions (page 1 of 2)