36
3 Operating the SAMMS-MV Device
your actions before pressing the ENTER key a second time
to select the ON setting.
6.Repeat Step 3 if you select an incorrect setting.
7.If you are in the program mode, press and hold the (F)unction
key for several seconds to exit. The display will show Prog.
Press the UP or DOWN key to change to the display mode.
8.Press the (F)unction key to go to other functions.
F12 - Ground Fault Protection or Warning
1.Press the LIST key to view the active ground fault detection
setting (ON or OFF). The factory default setting is warning
(OFF), and the other setting is protection (ON).
a.When warning (OFF) is selected, the Ground Fault LED
flashes if the ground current increases beyond the pickup
level. The LED stops flashing as soon as the current drops
below the pickup level.
b.When protection (ON) is selected, a ground current above
the pickup level will cause a trip. The motor stops, and the
Ground Fault LED is steadily lit. You must reset the unit
before the motor can be restarted.
2.To change the setting, you must be in program mode.
3.To change the setting, press the UP or DOWN key to display
the setting options, then press ENTER to select the setting
that is shown. The display blanks while the ENTER key is
pressed.
4.Repeat Step 3 if you select an incorrect setting.
5.To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6.Press the (F)unction key to go to other functions.
F12A - Ground Fault Pickup Current
1.Press the LIST key to view the active ground fault pickup
current in use. The range of values and default values are
shown in the table below:

Size Pickup Current Default

H3A-H3C 7A-I 10A

H6 7A-I 20A

2.To change the setting, you must be in program mode.
3.To change the setting, press the UP or DOWN key to display
the setting options, then press ENTER to select the setting
that is shown. The display blanks while the ENTER key is
pressed.
4.Repeat Step 3 if you select an incorrect setting.
5.To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6.Press the (F)unction key to go to other functions.
F13 - Set Programmable Timer #1
1.Press the LIST key to view the active setting for timer #1. The
default setting is OFF. If the timer is not used in the control
circuit, OFF is displayed and the UP, DOWN, and ENTER
keys are disabled. OFF is also displayed for a setting of 0
seconds. The timer may be adjusted from 0 - 200 seconds
in one second increments.
2.To change the setting, you must be in program mode.
3.To change the setting, press the UP or DOWN key until the
desired value is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
4.Repeat Step 3 if you select an incorrect setting.
5.To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6.Press the (F)unction key to go to other functions.
F14 - Set Programmable Timer #2
1.Press the LIST key to view the active setting for timer #2. The
default setting is OFF. If the timer is not used in the control
circuit, OFF is displayed and the UP, DOWN, and ENTER
keys are disabled. OFF is also displayed for a setting of 0
seconds. The timer may be adjusted from 0 - 200 seconds
in one second increments.
2.To change the setting, you must be in program mode.
3.To change the setting, press the UP or DOWN key until the
desired value is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
4.Repeat Step 3 if you select an incorrect setting.
5.To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6.Press the (F)unction key to go to other functions.
F15 - Display Current
1.Press the LIST key to view the instantaneous line currents or
the average instantaneous line current. (The LIST key is
disabled for full voltage, part-winding starters.) For instanta-
neous line currents, the display shows the phase designator
(A, b, or C) in the left-most character followed by three
significant digits of the value of the current. For the average
instantaneous line current, four digits are displayed without
a phase designator.
FLC
FLC