Subaru Robin Power Products RGV6100, RGV4100 AC Output Measuring, DC Output Measuring

Models: RGV4100 RGV6100

1 82
Download 82 pages 24.58 Kb
Page 32
Image 32

8-2 AC OUTPUT MEASURING

Fig. 8-8

Use a circuit like the shown in Fig.8-8 for measuring AC output. A hot plate or lamp with a power factor of

1.0may be used as a load. Adjust the load and rpm. and check that the voltage range is as specified in Table 8-2 at the rated amperage and rated rpm.

Rated voltage

120 V

240 V

 

 

 

Voltage range

108 -132 V

216 - 264 V

 

 

 

 

Table. 8-2

 

8-3 DC OUTPUT MEASURING

Fig. 8-9

Measurement of DC output is executed with the switch turned ON while the current is regulated at 8.3A by adjusting the load to the generator. If the voltage is within the range from 6V to 14V, the voltage output is normal.

NOTE : If a battery is connected as a load to the generator, the DC output voltage will increase by approximately 1 to 2 V. Therefore, carefully observe the electrolyte level and do not overcharge the battery.

- 29 -

Page 32
Image 32
Subaru Robin Power Products RGV6100, RGV4100 service manual AC Output Measuring, DC Output Measuring, Rated voltage 120 240