11. TROUBLESHOOTING

11-1 NO AC OUTPUT

11-1-1 CHECKING CONDENSER

(1) Check the capacity of condensers using a “Dr. Robin” generator tester in capacitance meter mode.

NOTE : Be sure to discharge condensers by shorting condenser leads each other before checking their capacitance, or the accurate reading cannot be obtained.

Fig. 11-1A Type RGV2800Fig. 11-1B Type RGV4100, RGV6100

NORMAL CAPACITY OF CONDENSER

RGV2800

RGV4100

RGV6100

 

 

 

24μF

20μF x 2

28μF x 2

 

 

 

 

Table. 11-1

 

(2)If such an instrument is unavailable, the condenser can be checked by replacing with a new one. If the generator performs good with new condenser, the cause of trouble is defect in original condenser.

11-1-2 CHECKING STATOR

(1)Remove control panel and disconnect stator wires at the connectors.

(2)Measure the resistance between terminals on stator leads. (See Fig.11-2) Refer to Table 9-1 for normal resistance.

If stator is faulty, replace it with a new one.

COUPLERSTATOR

Fig. 11-2

- 53 -

Page 56
Image 56