2. GENERATOR TROUBLESHOOTING

2-1 NO AC OUTPUT

2-1-1 CHECKING CONDENSER

(1) Check the capacity of condensers using a “Dr. Robin” generator tester in capacitance meter mode.

NOTE : Be sure to discharge condensers by shorting condenser leads each other before checking their capacitance, or the accurate reading cannot be obtained.

NORMAL CAPACITY OF

CONDENSER

RGV4101

RGV6101

 

 

20μF x 2

30μF x 2

 

 

Table. 2-1

(2)If such an instrument is unavailable, the con- denser can be checked by replacing with a new one. If the generator performs good with new condenser, the cause of trouble is defect in original condenser.

2-1-2 CHECKING STATOR

(1)Remove control panel and disconnect stator wires at the connectors.

(2)Measure the resistance between terminals on stator leads. (See Fig.2-2) Refer to Table 2-2 for normal resistance.

If stator is faulty, replace it with a new one.

Fig. 2-1

COUPLERSTATOR

Fig. 2-2

 

 

Specification

 

AC Winding

Condenser

MODEL

 

 

Winding

 

 

 

 

 

 

 

 

 

 

 

 

Hz

Voltage

 

White / Red

Black / Blue

Yellow / Yellow

 

 

 

 

 

 

 

RGV4101

60

120 V, 120 V / 240 V

 

0.54

0.54

1.20

 

 

 

 

 

 

 

RGV6101

60

120 V, 120 V / 240 V

 

0.22

0.22

0.46

 

 

 

 

 

 

 

 

 

Table. 2-2

 

 

 