(3)Check the insulation resistance between sta- tor core and each stator lead using a Dr. Robin generator tester in megger tester mode or a megger tester. (Fig. 11-3)

If insulation is bad, replace stator with a new one.

Fig. 11-3

11-1-3 CHECKING ROTOR

(1) Remove rear cover and stator.

(2) Using a Dr. Robin or a circuit tester, measure

 

 

 

the resistance of the field coil at the terminals.

 

 

Fig. 11-4

 

 

 

 

 

( Ω)

 

 

 

 

 

 

 

MODEL

RGV2800

RGV4100

RGV6100

 

 

 

 

 

 

 

 

 

RESISTANCE

1.75 Ω

1.77 Ω

 

1.60 Ω

 

 

 

 

 

 

 

 

Table. 11-2

NOTE : Because a diode is soldered to the coil ends at the terminals, resistance may be mea- sured only when tester probes touch the termi- nals in one combination of polarity. Therefore, if no resistance reading appears, try checking in reverse polarity.

[Remedy]

If the resistance is not normal, replace rotor with a new one.

Fig. 11-5

- 54 -