Sun Microsystems 816-7727-10 manual TABLE A-4 4-Post Cabinet Requirements Continued

Models: 816-7727-10

1 62
Download 62 pages 31.5 Kb
Page 61
Image 61
TABLE A-44-Post Cabinet Requirements (Continued)

TABLE A-44-Post Cabinet Requirements (Continued)

Cabinet Feature

Requirement

 

 

Airflow

The server operating airflow is 92 cfm, regardless

 

of ambient air and altitude. This airflow provides

 

appropriate cooling up to 104o F (40o C) and 10,000

 

feet (3000 meters).

 

For proper ventilation of the server, the front and back

 

doors must comply with the following minimum open area

 

requirements.

 

• 60 percent of the area of the front door that is directly in

 

front of the server must be open.

 

• 63 percent of the area of the back door that is directly

 

behind the server must be open.

 

• Maintain a minimum of 1.5 inches (3.8 cm) clearance

 

between the server and any front or back doors.

 

If the doors of the cabinet do not meet the open area

 

requirements, remove the door or doors that do not comply.

Vertical mounting rails

The cabinet must have two pairs of vertical mounting rails

 

(one pair in front, one pair in back) that conform to the EIA

 

(RETMA) standard for mounting hole spacing.

 

Left-side-to-right-side rail spacing (mounting hole center to

 

mounting hole center) for front and back rails must be 17.72

 

inches (45 cm).

 

Front-to-back rail spacing must be at least 23 inches (58.42

 

cm) and not more than 34.5 inches (87.63 cm) from the

 

outside face of the front rail to the outside face of the back

 

rail.

 

Front and back vertical rail mounting faces must be parallel

 

with each other and with the front plane of the rack.

EMI shielding

Electromagnetic interference (EMI) shielding requirements

 

are met by the system chassis and metal side panels, which

 

remain in place when the server is rackmounted.

Minimum service access

An area not less than 3 feet (1 meter) deep and

 

6 feet (2 meters) wide must be available in front of

 

the cabinet, for installation and service access.

Fire containment

The cabinet must meet Underwriters Laboratories, Inc., and

 

TUV Rheinland of N.A. requirements for fire containment.

 

 

Appendix A Background and Reference 53

Page 61
Image 61
Sun Microsystems 816-7727-10 manual TABLE A-4 4-Post Cabinet Requirements Continued