Sunway NT 10000 user manual · Connection, Important Information

Models: NT 10000

1 82
Download 82 pages 31.2 Kb
Page 29
Image 29

· Connection

The PV generator is connected by means of the externally accessible, touch-safe Tyco Solarlok connectors included in the con- signment. The Tyco Solarlok connectors are designed for a cable cross-section of 4 mm2 and have to be crimped. For further infor- mation, please read chapter 4.2 «Tyco Solarlok Connectors».

Please note:

All PV generator inlets are positioned in pairs. Inlet 1 is left, inlet 2 is in the middle, and inlet 3 is right. The upper connections are «POSITIVE», and the lower ones are «NEGATIVE».

Illustr.: PV generator connection via Tyco Solarlok connectors

Important Information

￿!

· The DC voltage can reach up to 850 V. The device may only be opened by a

qualified electrician!

 

 

 

· As soon as the PV generator has been

GB

connected to the Solar Inverter by means

 

of the DC connectors and the PV genera-

 

tor has been switched on, the PV genera-

 

tor voltage is applied internally!

 

·Please note that the inlet capacitors are still live, even after the PV generator has been switched off or the PV generator connector has been pulled out!

·After the AC and DC sides have been isolated, the Solar Inverter remains live for up to approximately five minutes!

·Therefore, wait at least five minutes for the internal voltage to discharge. Prior to working on the Solar Inverter, always

113

Page 29
Image 29
Sunway NT 10000 user manual · Connection, Important Information