Grid voltage monitoring

Earth-fault monitoring

Insulation monitoring Frequency monitoring DC monitoring Outlet characteristics

Grid connection fuse rating

Required number of phases per grid connection Number of injection phases (230 V single-phase)

Three phase according to E DIN VDE 0126-1-1 AFI (universal sensitive) according to E DIN VDE 0126-1-1

Yes, according to E DIN VDE 0126-1-1 Yes, according to E DIN VDE 0126-1-1 Yes, according to E DIN VDE 0126-1-1 Current source

3 x 25 A

3

3

Data interfaces

RS232, RS485, USB

Sensor interfaces

Irradiation, temperature

Display

LCD, 2 x 16 characters, 100 x 25 mm screen size

Level of protection against environmental factors Max. relative air humidity

Cooling

Ambient temperature (Celsius) Dimensions (height x width x depth) Weight

IP 54

95 percent

Ventilator above back panel, 2-chamber system -25° C to 40° C

max. 805 x 500 x 175 (height x width x depth) 30 kg (without assembly frame)

Subjekt to technical changes.

159

Page 75
Image 75
Sunway NT 10000 user manual 159