Installation Site Requirements

· Mechanical Load-Bearing Capacity

During assembly, please keep in mind that the Solar Inverter weighs 30 kg. The assembly foundation must be solid and capable of bearing the weight in the long run.

· Thermal Interaction

The assembly foundation must be made of flame-retardant material (unsuitable: wooden or plastic foundation; suitable: concrete and masonry), because the frame of the Solar Inverter can reach up to 70° C.

Maintain a minimum distance of 300 mm to other devices, cabinets, ceilings, cable channels, etc. above, below, and next to the housing.

The Solar Inverter must be installed in an upright position to ensure unobstructed convection.

Do not install several Solar Inverters on top of each other, as they might heat each other up.

If the Solar Inverter is installed in a switch cabinet, make sure the heat is removed to a sufficient degree.

The ambient temperature may not drop below -25° C or rise above +40° C.

To protect the Solar Inverter from unneces- sary external heat sources, do not expose the Solar Inverter to direct sunlight.

GB

·Protection from Moisture and Foreign Objects

Thanks to the high protection level IP 54, the Solar Inverter can be installed indoors as well as in a sheltered outdoor area, but it may not be directly exposed to rain.

Make sure the dust filter on the lower left side is not clogged by contamination.

That would impair the intake of cooling air. Depending on the surroundings, the filter should be cleaned at regular intervals.