3.7Error Display

Your Solar Inverter works fully automatically. Should external or internal factors neverthe- less lead to an error, an error number will be flagged on the display. Below, you will find a description of the error for each error number. If three consecutive error numbers are listed in the description, each of them refers to an energy unit of the Solar Inverter. E. g. for the description of errors 004 to 006, this means:

·Error 004 refers to:

DC inlet 1 (left DC connection)

energy unit 1 (lower control circuit board) grid phase L1

·Error 005 refers to:

DC inlet 2 (middle DC connection)

energy unit 2 (middle control circuit board) grid phase L2

·Error 006 refers to:

DC inlet 3 (right DC connection)

energy unit 3 (upper control circuit board) grid phase L3

Errors 001 to 003

· DC overvoltage

A maximum PV generator no-load voltage of 850 V is admissible. All components of the DC inlet have a sufficient safety factor. If this limit is exceeded, the Solar Inverter will stop the injection, and «error 001» will be flagged, for example. That means an over- voltage of the PV generator on inlet 1 or on

the lower energy unit.

 

GB

 

 

 

Errors 004 to 006

 

 

 

 

 

· Frequency fault

 

 

The Solar Inverter continuously monitors

 

 

the applied grid frequency. Should it be

 

 

outside the range specified in E DIN VDE

 

 

0126-1-1, the Solar Inverter will stop the

 

 

injection, and «error 004» will be flagged,

 

 

for example. That means a grid frequency

 

 

error on grid phase L1 or on the lower

 

 

energy unit.

 

 