Engineer’s Menu 1

TS690R Installation Manual

 

 

Panel Outputs [1.1]

Outputs 1 - 3 on the control panel and remote keypad outputs 5 - 8 can be programmed to any of the output types shown on pages 24 to 26. In addition, all panel outputs can be inverted, see “Configuration option 14” on page 32.

E / MENU 1

1

PANEL -

Enter output No. 1 - 8

e.g. 1

Programmable Output Types

No Type/Description

000Bell On

Activates when the main Bell trigger is on and deactivates at the end of the Bell Duration time or when the alarm is cancelled by the user.

001Strobe On

Activates when the Strobe trigger is on, and deactivates when the alarm is cancelled by the user.

002Switch 12V

Activates when the system is set and deactivates when an alarm occurs or the system is unset. This output is normally used for latching detectors.

Type No.

004

003 Detector Reset

Normally active at all times and deactivates

for 3 seconds when a valid passcode is

Enter new output type e.g. 021

021

Panel Outputs Flowchart

entered prior to setting the system. This output

is normally used for detector that required

power to be removed in order to reset them,

e.g., smoke detectors.

004Walk Test

Activates when the "Walk Test" option is selected and deactivates when the "Walk Test" option is finished.

005Alarm

Activates when an intruder alarm is detected and deactivates when the alarm is reset or aborted.

006P.A.

Activates when a PA alarm is detected and deactivates when the alarm is reset.

007Fire

Activates when a Fire alarm is detected and deactivates when the alarm is reset.

008System Set

Activates when any ward is set and deactivates when the system is fully unset.

009Code Accepted

Activates for 10 seconds following entry of any valid passcode.

01024 Hour

Activates when a 24Hr alarm is detected and deactivates when the alarm is reset.

24