Engineer’s Menu 1 | TS690R Installation Manual |
|
|
No Type/Description
03724hr cct Omitted
Activates when one or more 24 Hour circuits are omitted.
038Sounder Control
Normally used as the 0V connection for an extension loudspeaker so that only system alarm tones are generated.
039Call Engineer
Activates when the system requires an "Engineer Reset", deactivates when the system is reset by the engineer or "Remote Reset".
040General Fault
Activates during battery fault or when the system is prevented from being set. Deactivates when all faults are cleared.
041Battery Test
Activates for 1 minute on the hour every hour. This output is used to test the battery in remote PSU using a 519FM monitor PCB).
042Fob Active
Activates when the 525r remote setting device is used.
043System Full Set
Activates when all areas within the system are set and deactivates when any area is unset.
100 - 137 Circuit Mimic
Will mimic (active when circuit is active) circuits 01 to 38 respectively.
200 - 237 Circuit Alarms
Active when a circuit causes an alarm, for circuits 01 to 38 respectively.
Program Circuits [1.4]
The TS690R can monitor up to 38 detection circuits. Each circuit must be programmed in order for the system to respond correctly.
Circuit Types
The circuit type defines how the circuit will respond when it is triggered. The following circuit types are available:
0Not Used
A circuit that will never generate any alarm.
1Night
A circuit that will generate a full alarm when the system is set.
224hr
A circuit which is monitored at all times. When triggered in the unset condition a local alarm is generated and when triggered in the set condition a full alarm is generated.
3PA Silent
A circuit which is monitored at all times. When triggered it will activate any outputs that are programmed as P.A.
4PA Audible
A circuit which is monitored at all times. When triggered it will activate any outputs that are programmed as P.A. and generate a full alarm condition.
5Fire
A circuit that is normally connected to a smoke detector. When triggered it will generate a fire tone on the internal sounders, the external sounders are pulsed for the bell duration and any outputs programmed as fire will be activated.
6Auxiliary
A circuit which is monitored at all times. When triggered it will activate any outputs programmed as Auxiliary.
7Final Exit
This must be the first detector or door contact that is triggered when entering the protected area. When the setting mode for the system is programmed for Final Exit setting, opening and closing of this circuit during the exit procedure will cause the system to set. Once set, activation of this circuit will start the entry timer.