TS690R Installation Manual

Engineer’s Menu 1

 

 

06Bell Duration

This controls the duration of the external bell/sounder. If the timer is set to 199 the bell output is continuous. This timer has a working range of 000-199 minutes.

07Bell Delay

This timer delays the activation of the external bell/sounder and internal sounders. This timer has a working range of 000-199 minutes. Note: Any alarm during the entry procedure will cancel the bell delay.

08Double Knock Delay

This is the “Double Knock” time window in which either two circuit activation must occur within this time to generate an alarm condition. Or the circuit must remain active for the whole duration of this time to generate an alarm condition. This will only apply to circuits with the “Double Knock” attribute. This timer has a working range of 000-199 seconds.

09Test Time

This timer varies the number of days that “Test” attribute may be applied to a circuit. If the timer is set to 000 then circuits will remain on test until the “Test” attribute is removed. This timer has a working range of 000-030 days.

10Second Entry

When the “Entry Timer” has expired the “2nd Entry timer” starts to count down, if at the end of this time the system or area has not been unset then a full alarm will be generated. This timer has a working range of 000-199 seconds.

11Abort Delay

This timer sets the period in which the alarm signal may be aborted following an alarm condition. When an alarm occurs, the “Abort Output” (043) is only activated if the system is unset within this period. If the system is unset after this period the abort output is NOT activated. This timer has a working range of 000-199 seconds.

12Monitor Delay

This timer affects the duration of the “Timed Output” (No. 042). This timer has a working range of 000-199 minutes.

13Part Set Bell Delay

This is a "Part-Set Bell Delay" and operates as follows:

a)If the "Pset Com.Dly" is set to 000 and an alarm is activated whilst the system is part-set,

the "Bell Delay" timer is started. At the end of the bell delay the internal sounders are activated for the duration of the "Pset Bel.Dly". At the end of this delay the bell output is activated.

b)If the "Pset Com.Dly" is not set to 000 and an alarm is activated whilst the system is part-set, the "Bell Delay" timer is cancelled and the internal sounders are activated for the duration of the "Pset Bel.Dly". At the end of this delay the bell output is activated.

If the "Part Set Bell Delay" timer is set to 199 the bell output is not activated when an alarm occurs whilst the system is part set. This timer has a working range of 000 - 199 seconds.

14Courtesy Duration

This timer is used to control the duration of the output type “Courtesy Light”. This timer has a working range of 000-199 seconds.

15AC Off Delay

This timer delays the “audible” mains off indication when the mains power is removed. The display and any outputs programmed as “Mains Off” are not affected. This timer has a working range of 000-199 minutes.

E / MENU 1

5

TIMER --

Enter timer No.

e.g. 04 for exit time

030

Enter new timer value

e.g. 045

045

System Timers Flowchart

29