TS690R Installation Manual | Engineer’s Menu 1 |
|
|
06Bell Duration
This controls the duration of the external bell/sounder. If the timer is set to 199 the bell output is continuous. This timer has a working range of
07Bell Delay
This timer delays the activation of the external bell/sounder and internal sounders. This timer has a working range of
08Double Knock Delay
This is the “Double Knock” time window in which either two circuit activation must occur within this time to generate an alarm condition. Or the circuit must remain active for the whole duration of this time to generate an alarm condition. This will only apply to circuits with the “Double Knock” attribute. This timer has a working range of
09Test Time
This timer varies the number of days that “Test” attribute may be applied to a circuit. If the timer is set to 000 then circuits will remain on test until the “Test” attribute is removed. This timer has a working range of
10Second Entry
When the “Entry Timer” has expired the “2nd Entry timer” starts to count down, if at the end of this time the system or area has not been unset then a full alarm will be generated. This timer has a working range of
11Abort Delay
This timer sets the period in which the alarm signal may be aborted following an alarm condition. When an alarm occurs, the “Abort Output” (043) is only activated if the system is unset within this period. If the system is unset after this period the abort output is NOT activated. This timer has a working range of
12Monitor Delay
This timer affects the duration of the “Timed Output” (No. 042). This timer has a working range of
13Part Set Bell Delay
This is a
a)If the "Pset Com.Dly" is set to 000 and an alarm is activated whilst the system is
the "Bell Delay" timer is started. At the end of the bell delay the internal sounders are activated for the duration of the "Pset Bel.Dly". At the end of this delay the bell output is activated.
b)If the "Pset Com.Dly" is not set to 000 and an alarm is activated whilst the system is
If the "Part Set Bell Delay" timer is set to 199 the bell output is not activated when an alarm occurs whilst the system is part set. This timer has a working range of 000 - 199 seconds.
14Courtesy Duration
This timer is used to control the duration of the output type “Courtesy Light”. This timer has a working range of
15AC Off Delay
This timer delays the “audible” mains off indication when the mains power is removed. The display and any outputs programmed as “Mains Off” are not affected. This timer has a working range of
E / MENU 1
5
TIMER --
Enter timer No.
e.g. 04 for exit time
030
Enter new timer value
e.g. 045
045
System Timers Flowchart
29