Engineer’s Menu 1

TS690R Installation Manual

 

 

8Chime

Circuits with this attribute will cause the internal sounders and remote keypad sounders to generate a two tone “chime” sound if the circuit is activated. The users may enable or disable the chime feature, or select it to operate when the system is unset or part-set. The “Chime” attribute may only be assigned to Night, 24hr, Auxiliary, Final Exit and Exit Terminator circuit types.

E / MENU 1

4

CCT NO.--

Enter circuit No.

e.g. 04

 

 

 

 

 

 

 

 

 

 

 

 

 

NIGHT

 

Circuit Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter circuit type:

 

 

 

0

= Not Used

5

= Fire

1

= Night

6

= Auxiliary

2

= 24hr

7

= Final Exit

3= PA Silent 8 = Exit Terminator

4 = PA Audible 9 = Key Point

e.g. 7 for Final Exit

F.EXIT

 

Select attrib

 

 

1

= Access

5

= Reset

2

= D Knock

6

M

3

= Test

7

= Entry

4

= Omit

8

= Chime

e.g. 8 for chime

C

Program Circuits Flowchart

System Timers [1.5]

The system timers are as follows:

002nd Alarm Time

This timer controls the duration of the “Second Alarm” output. This timer has a working range of 000-199 seconds.

01No of Re-Arms

At the end of the bell duration time the system re-arms all circuits that are healthy. Circuits that are still in an alarm are isolated until they change to a healthy condition. This counter controls the number of times that a "circuit" will re-arm before it is locked out of the system. This counter has a working range of 000-199.

02Settle Time

When setting the system by “Final Exit” or “Exit Terminator”, detectors that are on the exit route sometimes take 3-4 seconds to settle after activation. The delay programmed in this timer is used to allow these detectors to settle before the system or area is set. This timer has a working range of 000-199 seconds.

03Part Set Comms Delay

When the system is part-set the communication of an alarm signal to the central station can be delayed by the value set in this timer. If the timer is set to 199 the part-set communications are disabled. This timer has a working range of 000-199 seconds.

04Exit Time

This timer sets the delay between the user initiating the exit procedure and the system (or area) actually setting. If during the exit time an “Exit Terminator” circuit is activated the exit time is cancelled and the system sets immediately. This timer has a working range of 000-199 seconds.

05Entry Time

When the system is set or part-set, and the entry procedure is initiated, the entry timer starts to count down. If a valid user passcode has not been entered when the timer reaches zero, the internal sounders are activated and the “2nd Entry” timer is started. This timer has a working range of 000-199 seconds.

28