Appendix A Models T802, 802E Appendix A Menu Trees (Reference: 06530C DCN6418) A-22 Error! Unknown document property name.Error! Unknown document property name. Error! Unknown document property name.Error! Unknown document property name. Signal Name Bit or Channel Number Description
CO2_SPAN_VALVE 2, 6 8 0 = let CO2 span gas in
1 = let zero gas in
VENT_VALVE 6 9 0 = open vent valve
1 = close vent valve
10–15 Spare
Rear board primary MUX analog inputs
0–3 Spare
4 Temperature MUX
5 Spare
O2_CONC_SENSOR 4 6 O2 concentration sensor
SAMPLE_PRESSURE 7 Sample pressure
8 Spare
REF_4096_MV 9 4.096V ref erence from MAX6241
SAMPLE_FLOW 10 Sample flow rate
CO2_CONC_SENSOR 2 11 CO2 concentration sensor
12–13 Spare (thermocouple input?)
14 DAC MUX
REF_GND 15 Ground reference
Rear board temperature MUX analog inputs
BOX_TEMP 0 Internal box temperature
1 Spare
CO2_CELL_TEMP 2 2 CO2 sensor cell temperature
3 Spare
O2_CELL_TEMP 4 4 O2 sensor cell temperature
5–7 Spare
Rear board DAC MUX analog inputs
DAC_CHAN_1 0 DAC channel 0 loopback
DAC_CHAN_2 1 DAC channel 1 loopback
DAC_CHAN_3 2 DAC channel 2 loopback
DAC_CHAN_4 3 DAC channel 3 loopback
Rear board analog outputs
CONC_OUT_1,
DATA_OUT_1
0 Concentration output #1,
Data output #1
CONC_OUT_2,
DATA_OUT_2
1 Concentration output #2,
Data output #2
CONC_OUT_3 1
DATA_OUT_3
2 Concentration output #3,
Data output #3
TEST_OUTPUT,
DATA_OUT_4
3 Test measurement output,
Data output #4
07275B DCN6418