<Packed valve handling precautions>

FILE NO. SVM-03008

<Stripping length of connection cable>

Open the valve stem all the way out; but do not try to open it beyond the stopper.

Securely tighten the valve stem cap with torque in the following table:

Gas side

30 to 42 N·m

 

(9.52 mm)

(3.0 to 4.2 kgf·m)

 

 

 

 

Liquid side

16 to 18 N·m

 

(6.35 mm)

(1.6 to 1.8 kgf·m)

 

 

 

 

Service port

9 to 10 N·m

 

(0.9 to 1.0 kgf·m)

 

 

 

 

 

 

 

 

 

 

 

 

 

Hexagonal wrench

 

 

 

is required.

 

 

 

 

 

Terminal block

Connecting cable

1 2 3

10 10

30

Power cord

 

L

N

 

 

10

40

10

40

30

 

 

Earth line

Earth line

Connecting cable

Power cord

Fig. 9-3-8

9-3-4. Wiring connection

1.Remove the valve cover from the outdoor unit.

2.Connect the connecting cable to the terminal as identified with their respective matched numbers on the terminal block of indoor and outdoor unit.

3.When connecting the connecting cable to the outdoor unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prevent water coming in the outdoor unit.

4.Insulate the unused cords (conductors) from any water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.

 

Fig. 9-3-9

 

 

 

 

 

 

 

 

Model

RAS-13UKV-E2

 

 

 

 

 

 

 

 

 

 

Power source

50/60 Hz, 220 – 240 V Single phase

 

 

 

 

 

 

 

 

Maximum

11A

 

 

 

running current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation fuse

25A (D type

 

 

 

 

 

)

rating

 

 

 

 

 

 

 

 

 

Power cord

H07RN-F or 245 IEC66 (1.5 mm2

or more)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

Wrong wiring connection may cause some electrical parts burn out.

Be sure to comply with local codes on running the wire from indoor unit to outdoor unit (size of wire and wiring method etc).

Every wire must be connected firmly.

This installation fuse (25A D type ) must be used for the power supply line of this air conditioner.

If incorrect or incomplete wiring is carried out, it will cause an ignition or smoke.

Prepare the power supply for exclusive use with the air conditioner.

This product can be connected to the mains. Connection to fixed wiring: A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.

NOTE: Connecting cable

Wire type: More than H07RN-F or 245 IEC66 (1.0 mm2 or more)

– 50 –

Page 51
Image 51
Toshiba RAS-13UKV-E2 Packed valve handling precautions, Stripping length of connection cable, Wiring connection

RAS-13UAV-E2, RAS-13UKV-E2 specifications

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 air conditioning units represent a significant step forward in both comfort and energy efficiency. Designed for residential and light commercial use, these models are packed with features that cater to diverse climate control needs while adhering to modern standards of sustainability.

One of the standout features of both models is the implementation of inverter technology. This advanced system allows for more precise temperature control by adjusting the compressor speed based on the ambient temperature requirements. This not only enhances energy efficiency but also ensures a quieter operation compared to traditional air conditioning systems. As a result, users benefit from consistent comfort without the disruptive sounds often associated with cooling units.

The RAS-13UKV-E2 and RAS-13UAV-E2 also feature a high energy efficiency rating, which is crucial for reducing electricity bills. The Seasonal Energy Efficiency Ratio (SEER) is a vital measure of energy efficiency over an entire cooling season. Both units excel in this regard, making them an environmentally friendly choice. This is further supported by Toshiba's commitment to incorporating R32 refrigerant, known for its lower environmental impact compared to older refrigerants.

User convenience is enhanced with integrated smart controls. Both models are compatible with wireless remote control features, allowing for easy adjustments from a distance. This is complemented by programmable settings that let users schedule operation times, ensuring that the units run only when needed, which further optimizes energy consumption.

Design-wise, these air conditioners boast a sleek and modern appearance, making them a visually appealing addition to any room. They are constructed with durable materials that ensure longevity and reliability. Moreover, the filters are designed for easy maintenance, ensuring cleaner indoor air quality and prolonging the lifespan of the unit.

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 units also come equipped with advanced air purification technologies. These features help to reduce airborne pollutants and allergens, contributing to a healthier indoor environment. With exceptional cooling and heating capabilities, easy installation, and advanced features, these models are designed to meet the modern user's needs for comfort, efficiency, and health. Overall, they represent an excellent investment in both cooling technology and eco-friendly practices.