10-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E

<Check procedure>

1C

1E

Gas leakage,

 

Discharge temp. error,

disconnection of TS/TC

 

gas leakage

sensors (Check code 02, 1C)

 

(Check code 03, 1E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve drive check

 

 

NO

 

 

Is coil of the pulse modulation valve

(P.M.V.) correctly set?

 

 

YES

 

 

 

 

 

 

NO

Is connector of coil connected to inverter?

YES

Is positioning sound of valve (sound hitting to stopper) heard from valve when the air conditioner starts the operation after turning off power of the air conditioner once?

NOTE :

After all the operations stopped by the remote control, the power keeps

being supplied to outdoor unit for approx. 3 minutes. If operating the air NO

conditioner by remote control again just after all the operations stopped by the remote control, positioning of the valve is not performed when outdoor unit

is activated because supplying power to the outdoor unit is not interrupted. After positioning of the valve, activate the compressor and the outdoor fan. It takes approx. 7 seconds for positioning of the valve, and sound ticktack (hitting sound to stopper) is heard for approx. 0.5 seconds at least of that period. As the sound is low, check sound by using screwdriver, etc.

YES

Are temp. sensors of indoor/outdoor units correctly set to the holder?

NOTE :NO The temperature sensors which are used to control electronic control valve

include indoor heat exchanger sensor (TC), outdoor heat exchanger temp. sensor (TE), and outdoor suction temp. sensor (TS).

YES

Set it correctly.

Set it correctly.

Replace coil valve.

Set it correctly.

Gas amount check and valve clogging check

Remove TC sensor connector from the P.C. board in indoor unit.(Remove connector from the P.C. board.)

Operate the air conditioner in COOL mode by TEMP button (Pi sound is heard if keeping pushed for 10 seconds.). The operation enters temporary operation mode which fixes opening degree of P.M.V. and No. of revolution of compressor. Check condensation at outlet of P.M.V., and then check operating pressure from the service port.

Existence of condensation at outlet of P.M.V.

YES

If there is condensation at outlet (1/4 inch=

6.35mm valve side),

 

the valve is clogged.

Replace valve.

Check the operating pressure from service port, and add gas if pressure is low.

Add gas.

– 64 –

Page 65
Image 65
Toshiba RAS-13UKV-E2, RAS-13UAV-E2 service manual Check Code 1C Miswiring in indoor/outdoor units and 1E, Check procedure

RAS-13UAV-E2, RAS-13UKV-E2 specifications

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 air conditioning units represent a significant step forward in both comfort and energy efficiency. Designed for residential and light commercial use, these models are packed with features that cater to diverse climate control needs while adhering to modern standards of sustainability.

One of the standout features of both models is the implementation of inverter technology. This advanced system allows for more precise temperature control by adjusting the compressor speed based on the ambient temperature requirements. This not only enhances energy efficiency but also ensures a quieter operation compared to traditional air conditioning systems. As a result, users benefit from consistent comfort without the disruptive sounds often associated with cooling units.

The RAS-13UKV-E2 and RAS-13UAV-E2 also feature a high energy efficiency rating, which is crucial for reducing electricity bills. The Seasonal Energy Efficiency Ratio (SEER) is a vital measure of energy efficiency over an entire cooling season. Both units excel in this regard, making them an environmentally friendly choice. This is further supported by Toshiba's commitment to incorporating R32 refrigerant, known for its lower environmental impact compared to older refrigerants.

User convenience is enhanced with integrated smart controls. Both models are compatible with wireless remote control features, allowing for easy adjustments from a distance. This is complemented by programmable settings that let users schedule operation times, ensuring that the units run only when needed, which further optimizes energy consumption.

Design-wise, these air conditioners boast a sleek and modern appearance, making them a visually appealing addition to any room. They are constructed with durable materials that ensure longevity and reliability. Moreover, the filters are designed for easy maintenance, ensuring cleaner indoor air quality and prolonging the lifespan of the unit.

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 units also come equipped with advanced air purification technologies. These features help to reduce airborne pollutants and allergens, contributing to a healthier indoor environment. With exceptional cooling and heating capabilities, easy installation, and advanced features, these models are designed to meet the modern user's needs for comfort, efficiency, and health. Overall, they represent an excellent investment in both cooling technology and eco-friendly practices.