FILE NO. SVM-03008

 

 

 

 

 

 

 

 

 

 

 

 

 

Diagnosis/Process flowchart

 

Item

 

Contents

 

Summary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

B

 

 

C

 

 

 

 

 

 

Check

Check winding resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between phases of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor, and resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between outdoor frames by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

NG

 

 

using a tester.

OK if 10M

or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is not grounded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

winding of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor.

 

 

 

Is not short-circuited

}

OK if 0.51

0.57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between windings.

(Check by a digital tester.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Winding is not opened.

 

 

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

 

 

 

NG

fan motor

 

 

 

 

 

 

 

com-

 

Operation

Remove connector CN300 of

 

 

 

 

 

 

 

 

 

 

 

 

 

position

 

 

 

 

 

pressor.

 

 

the outdoor fan motor, turn on

 

 

 

 

 

 

 

 

 

 

 

 

 

detect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal.

 

 

 

 

 

 

 

 

 

 

 

 

the power breaker, and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

perform the operation. (Stops

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

though activation is

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prompted.)

 

 

 

 

 

 

 

 

outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check operation within 2

 

 

 

 

 

 

 

 

 

fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minutes 20 seconds after

 

 

 

 

 

 

 

 

motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

activation stopped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Output check of fan motor

a) One or two of three

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

position detect signal>

 

voltages should be 5 V,

 

 

 

 

 

 

 

 

 

 

 

board assembly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

While connecting connector

 

and others should be 0V.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5P (CN301) for position

 

(When all are 0V or 5 V,

 

 

 

 

 

Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

detection, using a tester,

 

it is not accepted.)

 

 

 

 

 

 

 

 

 

 

NG

 

 

 

 

 

 

 

 

 

 

 

 

measure voltage between

b) When rotating the fan

 

 

 

compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

winding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-5. Between 5-4 : 5 V

 

slowly with hands, the

 

 

 

resistance.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage between pins

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

should move from 0V to 5 V.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Check it with an analog

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

tester.)

 

 

 

control board.

 

 

 

compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-8. How to Check Simply the Main Parts

10-8-1. How to check the P.C. board (Indoor unit)

(1)Operating precautions

1)When removing the front panel or the P.C. board, be sure to shut off the power supply breaker.

2)When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.

3)When connecting or disconnecting the connec- tors on the P.C. board, hold the whole housing. Do not pull at the lead wire.

(2)Inspection procedures

1)When a P.C. board is judged to be defective, check for disconnection, burning, or discolora- tion of the copper foil pattern or this P.C. board.

2)The P.C. board consists of the following 2 parts

a.Main P.C. board part:

DC power supply circuit (5 V, 12 V, 15 V), Indoor fan motor control circuit, CPU and peripheral circuits, buzzer, and Driving circuit of louver.

b.Indication unit of infrared ray receiving Infrared ray receiving circuit, LED:

To check defect of the P.C. board, follow the procedure described below.

– 66 –

Page 67
Image 67
Toshiba RAS-13UKV-E2, RAS-13UAV-E2 How to Check Simply the Main Parts, Diagnosis/Process flowchart Contents Summary

RAS-13UAV-E2, RAS-13UKV-E2 specifications

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 air conditioning units represent a significant step forward in both comfort and energy efficiency. Designed for residential and light commercial use, these models are packed with features that cater to diverse climate control needs while adhering to modern standards of sustainability.

One of the standout features of both models is the implementation of inverter technology. This advanced system allows for more precise temperature control by adjusting the compressor speed based on the ambient temperature requirements. This not only enhances energy efficiency but also ensures a quieter operation compared to traditional air conditioning systems. As a result, users benefit from consistent comfort without the disruptive sounds often associated with cooling units.

The RAS-13UKV-E2 and RAS-13UAV-E2 also feature a high energy efficiency rating, which is crucial for reducing electricity bills. The Seasonal Energy Efficiency Ratio (SEER) is a vital measure of energy efficiency over an entire cooling season. Both units excel in this regard, making them an environmentally friendly choice. This is further supported by Toshiba's commitment to incorporating R32 refrigerant, known for its lower environmental impact compared to older refrigerants.

User convenience is enhanced with integrated smart controls. Both models are compatible with wireless remote control features, allowing for easy adjustments from a distance. This is complemented by programmable settings that let users schedule operation times, ensuring that the units run only when needed, which further optimizes energy consumption.

Design-wise, these air conditioners boast a sleek and modern appearance, making them a visually appealing addition to any room. They are constructed with durable materials that ensure longevity and reliability. Moreover, the filters are designed for easy maintenance, ensuring cleaner indoor air quality and prolonging the lifespan of the unit.

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 units also come equipped with advanced air purification technologies. These features help to reduce airborne pollutants and allergens, contributing to a healthier indoor environment. With exceptional cooling and heating capabilities, easy installation, and advanced features, these models are designed to meet the modern user's needs for comfort, efficiency, and health. Overall, they represent an excellent investment in both cooling technology and eco-friendly practices.