FILE NO. SVM-03008

 

Table 2-2-1 Thicknesses of annealed copper pipes

 

 

 

 

 

 

 

 

Thickness (mm)

 

 

 

 

 

Nominal diameter

Outer diameter (mm)

R410A

 

R22

 

 

 

 

 

1/4

6.35

0.80

 

0.80

 

 

 

 

 

3/8

9.52

0.80

 

0.80

 

 

 

 

 

1/2

12.70

0.80

 

0.80

 

 

 

 

 

5/8

15.88

1.00

 

1.00

 

 

 

 

 

(2)Joints

For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.

a)Flare Joints

Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.

Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 2-2-3 to 2-2-6 below.

b)Socket Joints

Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.

Thicknesses of socket joints are as shown in Table 2-2-2.

Table 2-2-2 Minimum thicknesses of socket joints

Nominal diameter

Reference outer diameter of

Minimum joint thickness

copper pipe jointed (mm)

(mm)

 

 

 

 

1/4

6.35

0.50

 

 

 

3/8

9.52

0.60

 

 

 

1/2

12.70

0.70

 

 

 

5/8

15.88

0.80

 

 

 

2-2-2. Processing of piping materials

When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.

(1)Flare Processing Procedures and Precautions

a)Cutting the Pipe

By means of a pipe cutter, slowly cut the pipe so that it is not deformed.

b)Removing Burrs and Chips

If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.

c)Insertion of Flare Nut

d)Flare Processing

Make certain that a clamp bar and copper pipe have been cleaned.

By means of the clamp bar, perform the flare processing correctly.

Use either a flare tool for R410A or conventional flare tool.

Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.

D

A

Fig. 2-2-1 Flare processing dimensions

– 6 –

Page 7
Image 7
Toshiba RAS-13UKV-E2, RAS-13UAV-E2 Thicknesses of annealed copper pipes, Thickness mm, Outer diameter mm R410A R22

RAS-13UAV-E2, RAS-13UKV-E2 specifications

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 air conditioning units represent a significant step forward in both comfort and energy efficiency. Designed for residential and light commercial use, these models are packed with features that cater to diverse climate control needs while adhering to modern standards of sustainability.

One of the standout features of both models is the implementation of inverter technology. This advanced system allows for more precise temperature control by adjusting the compressor speed based on the ambient temperature requirements. This not only enhances energy efficiency but also ensures a quieter operation compared to traditional air conditioning systems. As a result, users benefit from consistent comfort without the disruptive sounds often associated with cooling units.

The RAS-13UKV-E2 and RAS-13UAV-E2 also feature a high energy efficiency rating, which is crucial for reducing electricity bills. The Seasonal Energy Efficiency Ratio (SEER) is a vital measure of energy efficiency over an entire cooling season. Both units excel in this regard, making them an environmentally friendly choice. This is further supported by Toshiba's commitment to incorporating R32 refrigerant, known for its lower environmental impact compared to older refrigerants.

User convenience is enhanced with integrated smart controls. Both models are compatible with wireless remote control features, allowing for easy adjustments from a distance. This is complemented by programmable settings that let users schedule operation times, ensuring that the units run only when needed, which further optimizes energy consumption.

Design-wise, these air conditioners boast a sleek and modern appearance, making them a visually appealing addition to any room. They are constructed with durable materials that ensure longevity and reliability. Moreover, the filters are designed for easy maintenance, ensuring cleaner indoor air quality and prolonging the lifespan of the unit.

The Toshiba RAS-13UKV-E2 and RAS-13UAV-E2 units also come equipped with advanced air purification technologies. These features help to reduce airborne pollutants and allergens, contributing to a healthier indoor environment. With exceptional cooling and heating capabilities, easy installation, and advanced features, these models are designed to meet the modern user's needs for comfort, efficiency, and health. Overall, they represent an excellent investment in both cooling technology and eco-friendly practices.