Installation Manual |
•Attach a nut (3/8" (M10): not supplied) and the Ø1.3" (34 mm) washer (supplied) to each hanging bolt.
•Insert a washer on both sides of the T groove of the hanging bracket of the indoor unit, and hang the indoor unit.
•Check that the four sides of the indoor unit are level using a level vial (levelness: 0.2" (5 mm) or less).
•Detach the installation gauge (accessory) from the installation pattern.
•Using the installation gauge, check and adjust the positional relation between the indoor unit and the ceiling opening (1) (0.4” - 1.4” (10 - 35 mm): 4 sides) and the
(How to use the installation gauge is printed on the gauge.)
Indoor unit | (2) 0.5” - 0.7” |
(12 - 17 mm)
(1)0.4” - 1.4”
(10 - 35 mm)
Installation gauge
Ceiling board
REQUIREMENT
Before installation of the indoor unit, be sure to remove the cushion for transportation between the fan and the bell mouth. Running the unit without removing the
Hanging bolt 3/8” (M10)
Nut
3/8” (M10)
Eccentric washer (Accessory)
*Install with the marking “UP” facing up.
*Procure hanging bolts and nuts locally.
Washer (Accessory)
To prevent the bolt from falling off (for safety), be sure to set it just under the hanging bracket as shown in the figure.
Nut
3/8” (M10)
cushion may damage the fan motor.
Remove the 5 screws and detach the wire guard. Remove the cushion placed between fan and bell mouth. Attach back the wire guard.
Screw | Wire guard |
|
Screw
Clamp | Screw | Cushion | |
* Do not remove the | |||
| |||
clamp fixing screw on |
|
| |
the indoor unit. |
|
|
Level vial (levelness: 0.2” (5 mm) or less)
Indoor unit | Hanging bolt | |
|
|
|
Hanging
bracket
(1) 0.4” - 1.4”
(10 - 35 mm)
Installation gauge
(2) 0.5” - 0.7” (12 - 17mm)
Ceiling board