Toshiba RAV-SP180UT-UL „System interconnection wires and ground wire, „Remote Control Wiring

Models: RAV-SP180UT-UL

1 38
Download 38 pages 51.43 Kb
Page 22
Image 22
„System interconnection wires and ground wire

4-way Air Discharge Cassette Type

Installation Manual

„System interconnection wires and ground wire

1.Strip the wire ends.

System interconnection wire : 0.4” (10 mm)

Ground wire : 0.8” (20 mm)

2.Match the wire colors with the terminal numbers on the indoor and outdoor units’ terminal blocks and firmly screw the wires to the corresponding terminals.

3.Secure the ground wire with the ground screw.

4.Fix the wires with a cord clamp.

Unit: in (mm)

„Wiring on the ceiling panel

According to the Installation Manual of the ceiling panel, connect the connector (20P: White) of the ceiling panel to the connector (CN510: White) on P.C. board of the electric parts box.

„Remote Control Wiring

Strip off the wire approx. 0.4” (9 mm) to connect.

For a single system, use non polarity, 2 core wire for the remote control wiring. (2 x AWG 20)

0.8” (20)

1.2” (30)

L1 L2 S

0.4” (10)

Terminal block for remote control wiring of indoor unit

A

B

Remote control wire (Field procurement)

Terminal block

A

Remote

control

B

unit

 

 

Ground wire

Unit: in (mm) CAUTION

For the details of wiring/installation of the remote control, refer to the Installation Manual enclosed with the remote control.

„Wiring diagram

• Firmly tighten the screws of the terminal block.

Keep the wire length as shown in figure below when it is connected to the terminal block.

0.08” (2 mm) or less

System interconnection wire

Single system

Low voltage

Indoor unit

A B

Remote Outdoor

control unit

208/230-1-60

L1 L2 S „Wiring on the ceiling panel„Remote Control Wiring

High voltage

L1 L2 S

21-EN

– 21 –

Page 22
Image 22
Toshiba RAV-SP180UT-UL „System interconnection wires and ground wire, „Wiring on the ceiling panel, „Remote Control Wiring