Toshiba RAV-SP180UT-UL installation manual Procedure, wayAir Discharge Cassette Type

Models: RAV-SP180UT-UL

1 38
Download 38 pages 51.43 Kb
Page 31
Image 31
– 30 –

4-way Air Discharge Cassette Type

Procedure 7

After check of the changed contents, push Manual backgroundManual backgroundManual backgroundManual background button. (Setup is determined.) When pushing Manual background button, the display disappears and the status becomes the usual stop status. (When pushing Manual backgroundManual background button the operation from the remote control is not accepted for approx.

1 minute.)

*If the operation from the remote control is not accepted even 1 minute or more passed after pushing Manual backgroundManual background button, it is considered that the address setup is incorrect.

In this case, the automatic address must be again set up.

Therefore repeat procedure of the setup change from the Procedure 1.

To recognize the position of the corresponding indoor unit though the indoor UNIT No. is known

Check the position during operation stop. (Be sure to stop operation of the set.)

 

1

1,3

2

 

Installation Manual

Procedure 1

 

Push simultaneously +

buttons for 4 seconds

or more.

 

After a while, the display part flashes and the display appears as shown below.

In this time, the position can be checked because fan and louver of the indoor unit operate.

For the group control, the indoor UNIT No. is

displayed as [Manual backgroundManual backgroundManual background ] and fans and louvers of all the indoor units in the group control operate.

Check the displayed CODE No. is [01].

When the CODE No. is other than [01], push Manual backgroundManual background button to erase the display and repeat procedure from the first step.

(After pushing Manual backgroundManual background button, operation of the remote control is not accepted for approx. 1 minute.)

(* Display changes according to the model No. of indoor unit.)

Procedure 2

In the group control, every pushing Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background button, the indoor UNIT No. in the group control is displayed in order.

In this time, the position of the indoor unit can be confirmed because only fan and louver of the selected indoor unit operate.

(For a group control, No. of the firstly displayed indoor unit becomes the header unit.)

Procedure 3

After confirmation, push Manual backgroundManual background button to return the mode to the usual mode.

When pushing Manual background button, the display disappears and the status becomes the usual stop status.

(When pushing Manual backgroundManual background button the operation from the remote control is not accepted for approx. 1 minute.)

EN

– 30 –

30-EN

Page 31
Image 31
Toshiba RAV-SP180UT-UL installation manual Procedure, wayAir Discharge Cassette Type