„Check codes and parts to be checked

4-way Air Discharge Cassette Type

Installation Manual

„Check codes and parts to be checked

Wired

Wireless remote control

 

 

 

 

remote

 

 

 

 

Sensor block display of

 

 

 

Air

control

 

Judging

 

 

receiving unit

 

 

 

display

 

 

Main defective parts

Parts to be checked / error description

conditioner

 

 

 

 

device

 

 

 

 

 

 

 

status

Indication

Operation Timer

Ready

Flashing

 

 

 

 

 

 

 

 

GR

GR

OR

 

 

 

 

 

 

 

 

 

 

No header remote

 

Incorrect remote control setting --- The header remote

 

E01

 

 

 

 

control

Remote

control has not been set (including two remote controls).

*

 

 

 

 

 

 

 

 

 

 

Remote control

control

No signal can be received from the indoor unit.

 

 

 

 

 

 

 

 

 

 

 

communication error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote control

Remote

System interconnection wires, indoor P.C. board, remote

 

E02

 

 

 

 

control

*

 

 

 

 

transmission error

control

 

 

 

 

 

--- No signal can be sent to the indoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit-remote

 

Remote control, network adapter, indoor P.C. board ---

 

E03

 

 

 

 

control regular

Indoor

No data is received from the remote control or network

Auto-reset

 

 

 

 

 

communication error

 

adapter.

 

 

 

 

 

 

Indoor unit-outdoor

 

 

 

 

 

 

 

 

unit serial

 

System interconnection wires, indoor P.C. board,

 

 

 

 

 

 

communication error

 

 

E04

 

 

 

 

Indoor

outdoor P.C. board --- Serial communication error

Auto-reset

 

 

 

 

 

IPDU-CDB

 

between indoor unit and outdoor unit

 

 

 

 

 

 

communication error

 

 

 

E08

 

 

 

 

Duplicated indoor

Indoor

Indoor address setting error --- The same address as the

Auto-reset

 

 

 

 

addresses

self-address was detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote control address setting error --- Two remote

 

 

 

 

 

 

Duplicated header

Remote

controls are set as header in the double-remote control

 

E09

 

 

 

 

control.

*

 

 

 

 

remote controls

control

 

 

 

 

 

 

(* The header indoor unit stops raising alarm and follower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor units continue to operate.)

 

 

 

 

 

 

 

 

 

 

E10

 

 

 

 

CPU-CPU

Indoor

Indoor P.C. board --- Communication error between main

Auto-reset

 

 

 

 

communication error

MCU and motor microcomputer MCU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header indoor unit-

 

Indoor P.C. board --- Regular communication is not

 

 

 

 

 

 

indoor follower unit

 

 

E18

 

 

 

 

Indoor

possible between header and follower indoor units or

Auto-reset

 

 

 

 

regular communication

 

 

 

 

 

error

 

between twin header (main) and follower (sub) units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E31

 

 

 

 

IPDU communication

Outdoor

Communication error between IPDU and CDB

Entire stop

 

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit heat

 

Heat exchanger sensor (TCJ) , indoor P.C. board ---

 

F01

 

 

 

ALT

exchanger sensor

Indoor

Open-circuit or short-circuit of the heat exchanger sensor

Auto-reset

 

 

 

 

 

(TCJ) error

 

(TCJ) was detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit heat

 

Heat exchanger sensor (TC), indoor P.C. board --- Open-

 

F02

 

 

 

ALT

exchanger sensor (TC)

Indoor

circuit or short-circuit of the heat exchanger sensor (TC)

Auto-reset

 

 

 

 

 

error

 

was detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit discharge

 

Outdoor temp. sensor (TD), outdoor P.C. board --- Open-

 

F04

 

 

 

ALT

temp. sensor (TD)

Outdoor

circuit or short-circuit of the discharge temp. sensor was

Entire stop

 

 

 

 

 

error

 

detected.

 

 

 

 

 

 

Outdoor unit temp.

 

Outdoor temp. sensors (TE/TS), outdoor P.C. board ---

 

F06

 

 

 

ALT

Outdoor

Open-circuit or short-circuit of the heat exchanger temp.

Entire stop

 

 

 

sensor (TE/TS) error

 

 

 

 

 

 

sensor was detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F07

 

 

 

ALT

TL sensor error

Outdoor

TL sensor may be displaced, disconnected or short-

Entire stop

(F06)

 

 

 

circuited.

 

 

 

 

 

 

 

F08

 

 

 

ALT

Outdoor unit outside

Outdoor

Outdoor temp. sensor (TO), outdoor P.C. board --- Open-

Operation

 

 

 

air temp. sensor error

circuit or short-circuit of the outdoor air temp. sensor was

continued

 

 

 

 

 

 

detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit room temp.

 

Room temp. sensor (TA), indoor P.C. board --- Open-

 

F10

 

 

 

ALT

Indoor

circuit or short-circuit of the room temp. sensor (TA) was

Auto-reset

 

 

 

 

 

sensor (TA) error

 

detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F12

 

 

 

ALT

TS sensor error

Outdoor

TS sensor may be displaced, disconnected or short-

Entire stop

(F06)

 

 

 

circuited.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F13

 

 

 

ALT

Heat sink sensor error

Outdoor

Abnormal temperature was detected by the temp. sensor

Entire stop

(L29)

 

 

 

of the IGBT heat sink.

 

 

 

 

 

 

 

F15

 

 

 

ALT

Temp. sensor

Outdoor

Temp. sensor (TE/TS) may be connected incorrectly.

Entire stop

(F06)

 

 

 

connection error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F29

 

 

 

SIM

Indoor unit, other P.C.

Indoor

Indoor P.C. board --- EEPROM error

Auto-reset

 

 

 

board error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN

– 34 –

34-EN