Ceiling height
Model RAV- | Possible installed ceiling height |
|
|
SP180, SP240 Type | Up to 12’6” (3.8 m) |
|
|
SP300, SP360, SP420 Type | Up to 15’1” (4.6 m) |
|
|
When the height of the ceiling exceeds the distance of the item
Therefore, it is necessary to change the setup value of the high ceiling switch or discharge direction.
▼Height list of ceiling possible to be installed
|
|
|
|
|
|
|
|
|
|
|
|
|
| Unit : ft (m) |
Model RAV- |
| SP180 Type |
|
| SP240 Type |
| SP300, SP360, SP420 Type | High ceiling setup | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
No. of discharge direction |
|
|
| Set data | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard (Factory default) | 9’2” |
| 10’6” |
| 11’6” | 9’10” |
| 10’10” |
| 11’10” | 12’10” | 13’9” | 14’9” | 0000 |
(2.8) |
| (3.2) |
| (3.5) | (3.0) |
| (3.3) |
| (3.6) | (3.9) | (4.2) | (4.5) | ||
|
|
|
|
|
| |||||||||
High ceiling (1) | 10’6” |
| 11’6” |
| 12’6” | 10’10” |
| 11’6” |
| 12’6” | 13’9” | 14’5” | 15’1” | 0001 |
(3.2) |
| (3.5) |
| (3.8) | (3.3) |
| (3.5) |
| (3.8) | (4.2) | (4.4) | (4.6) | ||
|
|
|
|
|
| |||||||||
High ceiling (2) | 11’6” |
| 12’6” |
| — | 11’10” |
| 12’6” |
| — | 14’9” | 15’1” | — | 0003 |
(3.5) |
| (3.8) |
| (3.6) |
| (3.8) |
| (4.5) | (4.6) | |||||
|
|
|
|
|
|
|
|
|
REQUIREMENT
•When using the air conditioner with
Therefore, change the setting switch according to height of the ceiling.
•When using the high ceiling (1) or (2) with
The lighting time of the filter sign (notification of filter cleaning) on the remote control can be changed according to installation conditions.
When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room, the detection temperature of heating can be raised.
Refer to "8 Applicable Controls"in this manual for the setting procedure.
– 7 – |