Toshiba RAV-SP180UT-UL Wireless remote control, Procedure, Cooling test run, Heating test run

Models: RAV-SP180UT-UL

1 38
Download 38 pages 51.43 Kb
Page 33
Image 33
Wireless remote control

4-way Air Discharge Cassette Type

Installation Manual

Wireless remote control

Procedure 1

Turn on the power of the air conditioner. When power is turned on for the first time after installation, it takes approx. 5 minutes until the remote control becomes available. In the case of subsequent power-on, it takes approx. 1 minute until the remote control becomes available. Execute a test run after the predetermined time has passed.

Procedure 2

Push “ON/OFF” button on the remote control, select [COOL] or [HEAT] with “MODE” button, and then select [HIGH] with “FAN” button.

Procedure 3

Cooling test run

Heating test run

 

 

Set the temperature to 64 °F

Set the temperature to 86 °F

(18°C) with the temp. setup

(30°C) with the temp. setup

buttons.

buttons.

Procedure 4

Cooling test run

Heating test run

 

 

After confirming a signal

After confirming a signal

receiving sound “beep”

receiving sound “beep”

immediately set the

immediately set the

temperature to 66 °F (19°C)

temperature to 84 °F (29°C)

with the temp. setup buttons.

with the temp. setup buttons.

Procedure 5

Cooling test run

Heating test run

 

 

After confirming a signal

After confirming a signal

receiving sound “beep”

receiving sound “beep”

immediately set the

immediately set the

temperature to 64 °F (18°C)

temperature to 86 °F (30°C)

with the temp. setup buttons.

with the temp. setup buttons.

Procedure 6

Repeat procedures 4 5 4 5.

Indicators “Operation” (green), “Timer” (green), and “Ready” (orange) in the wireless receiver section flash in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash, repeat procedures 2 to 5.

Procedure 7

Upon completion of the test run, push “ON/OFF” button to stop operation.

<Overview of test run operations using the wireless remote control>

Cooling test run:

ON/OFF 64 °F (18 °C) 66 °F (19 °C) 64 °F (18 °C) 66 °F (19 °C) 64 °F (18 °C) 66 °F (19 °C)

64 °F (18 °C) (test run) ON/OFF

Heating test run:

ON/OFF 86 °F (30 °C) 84 °F (29 °C) 86 °F (30 °C) 84 °F (29 °C) 86 °F (30 °C) 84 °F (29 °C)

86 °F (30 °C) (test run) ON/OFF