4-way Air Discharge Cassette Type

Installation Manual

7 ELECTRICAL CONNECTION

WARNING

1.Using the specified wires, ensure to connect the wires, and fix wires securely so that the external tension to the wires do not affect the connecting part of the terminals.

Incomplete connection or fixation may cause a fire, etc.

2.Be sure to connect ground wire. (grounding work) Incomplete grounding cause an electric shock.

Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.

3.Appliance shall be installed in accordance with national wiring regulations.

Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire.

CAUTION

Consult local building codes, NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.

This indoor unit has no power cord.

If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke.

Be sure to install circuit breaker is not tripped by shock waves.

If circuit breaker is not installed, an electric shock may be caused.

Be sure to use the cord clamps attached to the product.

Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires when peeling them.

Use the power cord and system interconnection wire of specified thickness, type, and protective devices required.

REQUIREMENT

For power supply wiring, strictly conform to the Local Regulation in each country.

For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.

Never connect 208/230 V power to the terminal blocks (A, B etc.) for control wiring. (Otherwise, the system will fail.)

Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.

The coating may melt resulting in an accident.

Run the refrigerant piping line and control wiring line in the same line.

Do not turn on the circuit breaker of the indoor unit until vacuuming of the refrigerant pipes completes.

Remote control wiring

For single system, use 2 x AWG20 non polarity wire is used for the remote control wiring.

Wiring

1.Connect the connecting wire to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit.

(4 x AWG12)

2.Insulate the unsheathed redundant cords (conductors) with electrical insulation tape. Process them so that they do not touch any electrical or metal parts.

3.For inter-unit wiring, do not use a wire jointed to another on the way.

 

 

 

 

Wire Quantity x size

 

 

 

 

 

 

Indoor unit - Outdoor unit *1

 

3 x AWG12 (polar)

Ground

 

 

 

1 x AWG12 or thicker

 

 

 

 

 

 

Remote control

 

2 x AWG20 (non-polar)

 

 

 

 

 

*1 :Length of the system interconnection wires.

RAV-

SP180AT2

SP240AT2

SP300AT2 -

SP420AT2

 

 

 

 

 

 

 

 

 

 

Wire

164’1” (50

 

229’8” (70

246’1” (75 m) or

length

m) or less

 

m) or less

less

CAUTION

Use the same size wire for the field power supply wire and system interconnection wires when the outdoor unit is RAV-SP180AT2.

NOTE

Use copper supply wires.

Use UL wires rated 600 V for the system interconnection wires.

Use UL wires rated 300 V for the remote control wires.

19-EN

– 19 –

Page 20
Image 20
Toshiba RAV-SP180UT-UL installation manual Electrical Connection, Remote control wiring, Wiring

RAV-SP180UT-UL specifications

The Toshiba RAV-SP180UT-UL is a cutting-edge commercial air conditioning unit designed to deliver exceptional cooling and heating performance. As part of Toshiba's advanced lineup of air conditioning systems, this model caters to diverse applications such as offices, retail spaces, and other commercial environments, ensuring comfortable conditions year-round.

One of the standout features of the RAV-SP180UT-UL is its powerful inverter technology. This technology enables the unit to adjust its cooling or heating output based on the current load requirements, resulting in significant energy savings and improved efficiency compared to conventional systems. It operates with a high Seasonal Energy Efficiency Ratio (SEER) and a Heating Seasonal Performance Factor (HSPF), making it an environmentally friendly choice for businesses seeking to reduce their carbon footprint.

Another key characteristic of the RAV-SP180UT-UL is its ultra-quiet operation. The unit is designed to minimize noise levels, providing a serene indoor environment that is ideal for workplaces and customer-facing areas. This low-noise performance is achieved through advanced fan engineering and acoustic insulation, ensuring that disruptions to work or leisure activities are kept to a minimum.

The RAV-SP180UT-UL also features flexible installation options, allowing for wall-mounted or ceiling-mounted configurations to suit various spatial requirements. Its compact design means that it can be installed in tight spaces without compromising on performance or aesthetics. The unit is equipped with a remote control for added convenience, enabling users to easily adjust settings, set timers, and switch between modes.

Moreover, the Toshiba RAV-SP180UT-UL is built with durability in mind. It utilizes high-quality materials and components that ensure long-lasting performance, even in demanding environments. The unit is also equipped with advanced filtration systems that enhance indoor air quality by removing dust, allergens, and other contaminants, contributing to a healthier workplace.

In summary, the Toshiba RAV-SP180UT-UL is a reliable and efficient solution for commercial air conditioning needs. Its inverter technology, quiet operation, flexible installation, and emphasis on durability make it a compelling choice for businesses looking to enhance comfort while maintaining energy efficiency. Whether for heating or cooling, this unit delivers consistent performance that meets the demands of modern commercial settings.