4-way Air Discharge Cassette Type

Installation Manual

6 REFRIGERANT PIPING AND EVACUATING

„Refrigerant Piping

1.If the outdoor units are to be mounted on a wall, make sure that the supporting platform is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.

2.Use copper pipe with 0.03" (0.8 mm) or more thickness. (In case pipe size is Ø5/8" (15.9 mm), with 0.04" (1.0 mm) or more.)

3.Flare nut and flare works are also different from those of the conventional refrigerant.

Take out the flare nut attached to the main unit of the air conditioner, and use it.

REQUIREMENT

When the refrigerant pipe is long, provide support brackets at intervals of 8’2” - 9’10” (2.5 - 3 m) to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Remove dust and moisture from the inside of the connecting pipes.

2. Tight connection (between pipes and unit)

3. Evacuate the air in the connecting pipes using

VACUUM PUMP.

4. Check the gas leakage. (Connected points)

„Pipe size

Model

 

SP180

SP240, SP300,

RAV-

SP360, SP420

name

type

 

type

 

 

 

 

 

 

 

 

Gas side

1/2"

5/8"

 

(12.7 mm)

(15.9 mm)

Pipe size

 

 

 

 

Liquid side

1/4"

3/8"

 

 

(6.4 mm)

(9.5 mm)

 

 

 

 

 

 

„Permissible Piping Length and Height Difference

They vary according to the outdoor unit.

For details, refer to the Installation Manual attached to the outdoor unit.

Flaring

Cut the pipe with a pipe cutter. Remove burrs completely.

Remaining burrs may cause gas leakage.

Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.

However, the conventional

B

tools can be used by adjusting

 

projection margin of the

 

copper pipe.

 

Projection margin in

flaring : B (Unit : in (mm))

Rigid (Clutch type)

Outer dia. of copper

R410A tool

Conventional

used

tool used

pipe

 

 

R410A

R410A

 

 

 

 

1/4” (6.4), 3/8” (9.5)

 

0.06” - 0.08”

0 - 0.02”

(1.5 - 2.0)

 

1/2” (12.7), 5/8” (15.9)

(0 - 0.5)

0.08” - 0.1”

 

(2.0 - 2.5)

 

 

Flaring dia. meter size : A (Unit : in (mm))

Outer dia. of copper

A -+00,02"(–0,4)

pipe

 

R410A

 

 

1/4” (6.4)

0.36” (9.1)

 

 

3/8” (9.5)

0.52” (13.2)

 

 

1/2” (12.7)

0.65” (16.6)

 

 

5/8” (15.9)

0.78” (19.7)

 

 

* In case of flaring for R410A with the

 

 

A

 

conventional flare tool, pull it out approx.

 

 

 

 

 

 

 

 

 

 

0.02" (0.5 mm) more than that for R22 to

 

 

 

 

 

 

 

 

 

 

adjust to the specified flare size.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The copper pipe gauge is useful for

 

 

 

 

 

adjusting projection margin size.

 

 

 

 

 

Tightening connection

CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

EN

– 16 –

16-EN

Page 17
Image 17
Toshiba RAV-SP180UT-UL installation manual Refrigerant Piping and Evacuating, „ Refrigerant Piping, „Pipe size

RAV-SP180UT-UL specifications

The Toshiba RAV-SP180UT-UL is a cutting-edge commercial air conditioning unit designed to deliver exceptional cooling and heating performance. As part of Toshiba's advanced lineup of air conditioning systems, this model caters to diverse applications such as offices, retail spaces, and other commercial environments, ensuring comfortable conditions year-round.

One of the standout features of the RAV-SP180UT-UL is its powerful inverter technology. This technology enables the unit to adjust its cooling or heating output based on the current load requirements, resulting in significant energy savings and improved efficiency compared to conventional systems. It operates with a high Seasonal Energy Efficiency Ratio (SEER) and a Heating Seasonal Performance Factor (HSPF), making it an environmentally friendly choice for businesses seeking to reduce their carbon footprint.

Another key characteristic of the RAV-SP180UT-UL is its ultra-quiet operation. The unit is designed to minimize noise levels, providing a serene indoor environment that is ideal for workplaces and customer-facing areas. This low-noise performance is achieved through advanced fan engineering and acoustic insulation, ensuring that disruptions to work or leisure activities are kept to a minimum.

The RAV-SP180UT-UL also features flexible installation options, allowing for wall-mounted or ceiling-mounted configurations to suit various spatial requirements. Its compact design means that it can be installed in tight spaces without compromising on performance or aesthetics. The unit is equipped with a remote control for added convenience, enabling users to easily adjust settings, set timers, and switch between modes.

Moreover, the Toshiba RAV-SP180UT-UL is built with durability in mind. It utilizes high-quality materials and components that ensure long-lasting performance, even in demanding environments. The unit is also equipped with advanced filtration systems that enhance indoor air quality by removing dust, allergens, and other contaminants, contributing to a healthier workplace.

In summary, the Toshiba RAV-SP180UT-UL is a reliable and efficient solution for commercial air conditioning needs. Its inverter technology, quiet operation, flexible installation, and emphasis on durability make it a compelling choice for businesses looking to enhance comfort while maintaining energy efficiency. Whether for heating or cooling, this unit delivers consistent performance that meets the demands of modern commercial settings.