Toshiba RAV-SP180UT-UL „Evacuation, Refrigerant amount to be added, Piping with outdoor unit

Models: RAV-SP180UT-UL

1 38
Download 38 pages 51.43 Kb
Page 18
Image 18
▼Tightening torque of flare pipe connections

4-way Air Discharge Cassette Type

 

Unit : ft•lbs (N•m)

Outer dia. of copper pipe

Tightening torque

 

 

1/4" (6.4 mm)

10 - 13 (14 - 18)

 

 

3/8" (9.5 mm)

24 - 31 (33 - 42)

 

 

1/2" (12.7 mm)

37 - 46 (50 - 62)

 

 

5/8" (15.9 mm)

46 - 57 (63 - 77)

 

 

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.

Installation Manual

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor unit.

(Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Flare at indoor Installation Manual unit side

Refrigerant amount to be added Flare at Piping with outdoor unit„Evacuation outdoor unit side

Be sure to use a scale to charge the refrigerant of specified amount.

REQUIREMENT

Charging an excessive or too little amount of

 

refrigerant causes a trouble of the compressor.

 

Be sure to charge the refrigerant of specified

 

amount.

A personnel who charged the refrigerant should

 

write down the pipe length and the added

 

refrigerant amount in the nameplate attached to the

Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union Open the valve fullyGas leak checkThermal insulation process– 17 –Flare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

Piping with outdoor unit

Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit.

„Evacuation

Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.

For details, follow to the Installation Manual attached to the outdoor unit.

Never use the refrigerant sealed in the outdoor unit for air purge.

service panel of the outdoor unit. It is necessary to

troubleshoot the compressor and refrigeration cycle

malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4 mm hexagonal wrench is required for opening the valve. For details, refer to the Installation Manual attached to the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).

Thermal insulation process

Apply thermal insulation for the pipes separately at liquid side and gas side.

For the thermal insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 248 °F (120 °C) or higher.

Using the attached thermal insulation material, apply the thermal insulation to the pipe connecting section of the indoor unit securely without gap.

REQUIREMENT

Apply the thermal insulation to the pipe connecting section of the indoor unit securely up to the root

17-EN

– 17 –

Page 18
Image 18
Toshiba RAV-SP180UT-UL „Evacuation, Refrigerant amount to be added, Piping with outdoor unit, Open the valve fully