9 TEST RUN
Before test run
•Before turning on the circuit breaker, carry out the following procedure.
1)Using
1MΩ or more exists between the terminal block L1 to L2 and the ground (grounding).
If resistance of less than 1MΩ is detected, do not run the unit.
2)Check the valve of the outdoor unit being opened fully.
•To protect the compressor at activation time, leave
Execute a test run
Using the remote control, operate the unit as usual. For the procedure of the operation, refer to the attached Owner’s Manual.
A forced test run can be executed in the following procedure even if the operation stops by
CAUTION
•Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
Installation Manual
Wired remote control
![Execute a test run](/images/new-backgrounds/34989/3498963xi3.webp)
2, 4 ![2, 4 3](/images/new-backgrounds/34989/3498963xi5.webp)
![– 31 –](/images/new-backgrounds/34989/3498963xi6.webp)
3
1,5
Procedure 1
Keep button pushed for 4 seconds or more. [TEST] is displayed on the display part and the selection of mode in the test mode is permitted.
Procedure 2
Push button.
Procedure 3
Using button, select the operation mode, [COOL] or [HEAT].
•Do not run the air conditioner in a mode other than [COOL] or [HEAT].
•The temperature controlling function does not work during test run.
•The detection of error is performed as usual.
Procedure 4
After the test run, push button to stop a test run.
(Display part is same as procedure 1.)
Procedure 5
Push check button to cancel (release from) the test run mode.
([TEST] disappears on the display and the status returns to a normal.)