Toshiba RAV-SP180UT-UL „Using wireless remote control, „Installing indoor unit on high ceiling

Models: RAV-SP180UT-UL

1 38
Download 38 pages 51.43 Kb
Page 24
Image 24
„Using wireless remote control

4-way Air Discharge Cassette Type

Installation Manual

Procedure 3

Using temp. setup „Installing indoor unit on high ceiling / (1 → 2 → 3 → 4 → 5 → 6 ). buttons, specify CODE

No. [ Restore the factory default ].

Procedure 4

Using timer time – 23 – / Manual background buttons, select SET DATA

[ Manual backgroundManual background ].

Procedure 5

Push Manual backgroundManual background button. When the display changes from flashing to lit, the setup is completed.

To change settings of another indoor unit, repeat from Procedure 2.

To change other settings of the selected indoor unit, repeat from Procedure 3.

Use Manual background button to clear the settings.

To make settings after Manual background button was pushed, repeat from Procedure 2.

Procedure 6

When settings have been completed, push Manual background button to determine the settings.

When Manual backgroundManual background button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode.

(While “SETTING” is flashing, no operation of the remote control is accepted.)

„Using wireless remote control

Change the high-ceiling settings with the DIP switch on the receiver section P.C. board.

For details, refer to the manual of the wireless remote controller kit. The settings can also be changed with the switch on the indoor microcomputer P.C. board.

*However, once the setting is changed, setting to 0001 or 0003 is possible but setting to 0000 requires a setting data change to 0000 using the wired remote control (sold separately) with the normal switch setting (factory default).

Manual background SW501-1

SW501-2

Manual backgroundManual backgroundManual background MCU(IC501)

Setup data

SW501-1

SW501-2

 

 

 

0000

OFF

OFF

(Factory default)

 

 

0001

ON

OFF

 

 

 

0003

OFF

ON

 

 

 

„Installing indoor unit on high ceiling

When an indoor unit is installed on a ceiling higher than the standard height, make the high-ceiling setting for fan speed adjustment.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [5d].

Select the setting data for Procedure 4 from the “Height list of ceiling possible to be installed” table on page 7 in this manual.

Restore the factory default

To return the DIP switch settings to the factory default, set SW501-1 and SW501-2 to OFF, connect a separately sold wired remote control, and then set the data of CODE No. [5d] to “0000”.

23-EN

– 23 –

Page 24
Image 24
Toshiba RAV-SP180UT-UL „Using wireless remote control, „Installing indoor unit on high ceiling, 1 → 2 → 3 → 4 → 5 →