7. Operation in Status Monitor Mode

7. 1 Displaying details of an item monitored

1 Select/confirm the desired item using the control dial.

(Ex. Select/confirm “Output current”)

The monitor window of the item selected appears.

*Depending on the item selected, no monitor window may be displayed.

Functions of function keys

F1 : Brings you to the Top View Mode.

F4 : Brings you to the Parameter Setup Mode.

„How to use monitor windows

Monitor windows can be broadly classified under the following three types.

<Type of window 1: Displays a value and a graph>

This type of window displays an analog value, such as an output frequency, output current or output voltage. (Ex. “Output current”)

It displays the current value both numerically and in a graph form.

In addition, the minimum allowable value (min) and the maximum allowable value (max) are also displayed at the bottom of the window.

Status Monitor Mode

Output current

22%

min=0max=185

TopPrm

F1F4

Status Monitor Mode

Output current

22%

min=0max=185

TopPrm

<Type of window 2: Displays information in a graph form>

This type of window displays input/output terminal information and a life alarm in a graph form. (Ex. “Input terminal : S4, S3...R, F”)

It displays the ON/OFF status of each terminal signal and the ON/OFF status of an alarm signal in a graph form.

If the arrow is moved to a terminal or alarm symbol, the name of the function assigned to the terminal or the name of the alarm is displayed.

Status Monitor Mode

Input terminal 1 : S4,S3…R,F

S4 S3 S2 S1 RES ST R F

ON

OFF

Forward run

TopPrm

*This illustration shows the information displayed when the LCD panel is connected to an VF-AS1 inverter.

<Type of window 3: Displays information in a list form>

This type of window displays detailed trip information. (Ex. Past trip # 1 (latest))

It displays the conditions under which the inverter was operated at the occurrence of tripping.

Past trip # 1 (latest)

 

E

:Emergency stop

 

 

 

 

Sequence number

1

 

 

Output frequency

25.0Hz

 

Rotative direction

FWD

 

Frequency reference

30.0Hz

 

Output current

40%

 

Top

Prm

7-2

Page 27
Image 27
Toshiba RKP004Z instruction manual Displaying details of an item monitored