811. Before. Beforemaking a servicemakingcall a service call

If a problem occurs, follow the instructions in this table to track down and eliminate the cause of the problem.

Problems

Possible causes

Remedies

 

 

 

Nothing is displayed on the

• The inverter connected is not

• Check whether the inverter is turned

screen.

turned on or it is not connected

on.

 

securely.

• Check the interconnect cable and the

 

 

connector for loosening.

The Startup window

• A cable other than a dedicated

• Use a dedicated cable.

appears, but the message

one is used.

• Set the communication speed and the

“CONNECTION IN

• The communication speed

parity, as specified below.

PROGRESS” does not out

setting or parity setting of the

F800 (communication speed) = 1

and the screen does not turn

inverter is different from that of

(19,200 bps)

to the next window.

the unit.

F801 (parity) = 1 (even parity)

 

 

Then turn the unit off and then back on

 

 

to reset it.

Although line information is

• Connection may be broken

• Move to another window by pressing

displayed on the screen,

during communication.

the [ESC] key to reload textual

textual information is not

• If the unit uses an old language

information, and check the cable and

displayed. Or some

database, the codes shown

the connector for loosening.

characters are not displayed

below may be displayed.

• This phenomenon does not mean that

correctly.

<Ex.>

the unit is faulty.

 

“F123” “:004” “M301”

 

The error code E-17 (key

• The same key is pushes more

• Check whether the key operates

failure alarm) is displayed.

than 20 seconds.

normally. If it does not operate

 

 

normally, it has to be repaired.

Operation cannot be

• Panel Operation mode is not

• Change the setting of the basic

controlled with the [RUN]

enabled.

parameter COMd (command input

key or the [STOP/RESET]

 

mode) to 1 (Panel / LCD-option).

key.

• The operation frequency is set

• Set an operation frequency according

 

at 0.0Hz.

to the setting of the basic parameter

 

 

FMOd (frequency input mode 1).

 

 

When performing operation at the

 

 

frequency set with the extension

 

 

operation panel (see section 5.1), set

 

 

FMOd to 4 (Panel / LCD-option).

Operation can be controlled

• The basic parameter Fr (panel

• Change the setting of the parameter Fr

with the [RUN] key and the

FWD/REV selection) is set to 0

(panel FWD/REV selection) to 2 or 3.

[STOP/RESET], but the

or 1.

 

direction of rotation cannot

 

 

be changed with the

 

 

[FWD/REV] key.

 

 

The inverter has tripped

• F803 (com time-out time) is

• Connection may be broken during

because of a communication

turned ON (enabled).

communication. Check the cable and

error (Err5).

* By default, the function of

the connector for loosening.

 

measuring the time for a

 

 

time-out is turned off (disabled).

 

Although the [STOP/RESET]

• Multiple commands have been

• Check to see if multiple commands

key was not pressed, the

entered because the three keys

have been entered as a result of

machine stopped operating.

[F2], [F3] and [F4] or [ESC],

pressing the three keys in rapid

 

[FWD] and [RUN] were pressed

succession.

 

in rapid succession.

• Check whether the key operates

 

• The [STOP/RESET] key may be

normally. If it does not operate

 

broken and held in the ON

normally, it has to be repaired.

 

position.

 