Figure 3: DIN Rail Mounting Kit Installation
3.2 Installation for Non-Toshiba ASD Networks
Note that in order to power the unit when not connecting to Toshiba ASDs via the common serial ports, the optional 120VAC/9VDC power supply (ICC part number 10456) or a
1.Mount the unit via the desired method (refer to section 3.1).
2.Connect the various networks to their respective plugs/terminal blocks. Ensure that any terminal blocks are fully seated into their respective headers, and route the network cables such that they are located well away from any electrical noise sources, such as ASD input power or motor wiring. Also take care to route all cables away from any sharp edges or positions where they may be pinched.
3.Take a moment to verify that the gateway and all network cables have sufficient clearance from electrical noise sources such as drives, motors, or
4.Connect the power supply to the gateway’s “AUX PWR” jack.
3.3 Toshiba Common Serial ASD Network Installation
The gateway connects to each drive via the drive’s common serial (logic level) communication port, typically located on either the main drive control board (G7, S11), on the front of the drive enclosure under a small