Parameter

 

Function / Title

Bank

Mask

Adjustment Range

 

Multiplier

 

 

 

 

 

 

 

 

0061

LOW SPEED SIGNAL

0 / 1

FFFF

0 Fmax

 

0.01

 

OUTPUT FREQ

 

 

 

 

 

0062

ACC/DEC COMPLETE

0 / 1

FFFF

0 Fmax

 

0.01

 

DETECT BAND

 

 

 

 

 

0063

SPEED REACH MAXIMUM

0 / 1

FFFF

0 Fmax

 

0.01

 

FREQUENCY

 

 

 

 

 

0064

SPEED REACH MINIMUM

0 / 1

FFFF

0 Fmax

 

0.01

 

FREQUENCY

 

 

 

 

 

0065

COMMERCIAL POWER/INV

0 / 1

00C0

0000: OFF

(0)

 

SWITCHING OUTPUT

 

 

0040: Auto switch on trip

(1)

 

 

 

 

 

 

0080: At COMMERCIAL POWER/

 

 

 

 

 

 

INV SWITCH FREQ

(2)

 

 

 

 

 

 

00C0: Both (1) and (2)

(3)

 

0066

2, 3

COMMERCIAL

0 / 1

FFFF

0 Fmax

 

0.01

 

POWER/INV

 

 

 

 

 

 

 

SWITCH FREQ

 

 

 

 

 

0067

“FP”

OUTPUT TERMINAL

0 / 1

0003

0000: 48f

(0)

 

PULSE FREQUENCY

 

 

0001: 96f

(1)

 

 

 

 

 

 

0002: 360f

(2)

 

0068

RR INPUT SPECIAL

0 / 1

00E0

0000: Standard

(0)

 

FUNCTION SELECT

 

 

0040: Fmax

(1)

 

 

 

 

 

 

0080: TACC/TDEC multiplier

(2)

 

 

 

 

 

 

00C0: VB multiplication factor

(3)

 

 

 

 

 

 

0020: CL multiplication factor

(4)

 

72