13.6.2 Supported Subpoints

This application contains a predefined set of FLN subpoints (refer to Table 4). These points are static for this application, and cannot be edited.

Table 4: Supported Subpoints

Point #

Point

Subpoint

Factory

Units

Slope

Intercept

On

Off

 

Type

Name

Default

 

 

 

Text

Text

01

LAO

ADDRESS

99

1

0

02

LAO

APPLICATION

2750

1

0

03

LAI

FREQ OUTPUT

0

HZ

0.01

0

04

LAI

OUTPUT CUR

0

A

0.01

0

05

LAI

OUTPUT VOLT

0

V

0.1

0

06

LAI

SPECIAL MON

0

-

1

0

07

LAO

MON SELECT

0

-

1

0

08

LAO

ACCEL TIME

50

SEC

0.1

0

09

LAO

DECEL TIME

100

SEC

0.1

0

10

LDO

CMD FWD.STOP

STOP

1

0

FWD

STOP

11

LDO

CMD REV.STOP

STOP

1

0

REV

STOP

12

LAO

FREQ CMD

0

HZ

0.01

0

13

LAO

MIN FREQ

0

HZ

0.01

0

-

-

14

LAO

FREQ JUMP A

32767

HZ

0.01

0

-

-

15

LAO

FREQ JUMP B

32767

HZ

0.01

0

-

-

16

LDI

ALARM OUTPUT

0

1

0

ALARM

-

17

LDI

RUNNING

STOP

1

0

RUN

STOP

18

LAO

PID SET PNT

0

PCT

0.01

0

-

-

19

LDO

RESET CMD

0

1

0

RESET

-

20

LAO

OVRD TIME

1

HRS

1

0

21

LDI

ASD COMM

NO

-

1

0

YES

NO

22

LAO

OPER MODE

0

-

1

0

-

-

29

LDO

DAY.NIGHT

DAY

1

0

NIGHT

DAY

99

LAO

ERROR STATUS

0

1

0

Notes:

Points not listed are not used in this application.

All points have the same value for English units and SI units.

59