13.6.2 Supported Subpoints
This application contains a predefined set of FLN subpoints (refer to Table 4). These points are static for this application, and cannot be edited.
Table 4: Supported Subpoints
Point # | Point | Subpoint | Factory | Units | Slope | Intercept | On | Off |
| Type | Name | Default |
|
|
| Text | Text |
01 | LAO | ADDRESS | 99 | – | 1 | 0 | – | – |
02 | LAO | APPLICATION | 2750 | – | 1 | 0 | – | – |
03 | LAI | FREQ OUTPUT | 0 | HZ | 0.01 | 0 | – | – |
04 | LAI | OUTPUT CUR | 0 | A | 0.01 | 0 | – | – |
05 | LAI | OUTPUT VOLT | 0 | V | 0.1 | 0 | – | – |
06 | LAI | SPECIAL MON | 0 | - | 1 | 0 | – | – |
07 | LAO | MON SELECT | 0 | - | 1 | 0 | – | – |
08 | LAO | ACCEL TIME | 50 | SEC | 0.1 | 0 | – | – |
09 | LAO | DECEL TIME | 100 | SEC | 0.1 | 0 | – | – |
10 | LDO | CMD FWD.STOP | STOP | – | 1 | 0 | FWD | STOP |
11 | LDO | CMD REV.STOP | STOP | – | 1 | 0 | REV | STOP |
12 | LAO | FREQ CMD | 0 | HZ | 0.01 | 0 | – | – |
13 | LAO | MIN FREQ | 0 | HZ | 0.01 | 0 | - | - |
14 | LAO | FREQ JUMP A | 32767 | HZ | 0.01 | 0 | - | - |
15 | LAO | FREQ JUMP B | 32767 | HZ | 0.01 | 0 | - | - |
16 | LDI | ALARM OUTPUT | 0 | – | 1 | 0 | ALARM | - |
17 | LDI | RUNNING | STOP | – | 1 | 0 | RUN | STOP |
18 | LAO | PID SET PNT | 0 | PCT | 0.01 | 0 | - | - |
19 | LDO | RESET CMD | 0 | – | 1 | 0 | RESET | - |
20 | LAO | OVRD TIME | 1 | HRS | 1 | 0 | – | – |
21 | LDI | ASD COMM | NO | - | 1 | 0 | YES | NO |
22 | LAO | OPER MODE | 0 | - | 1 | 0 | - | - |
29 | LDO | DAY.NIGHT | DAY | – | 1 | 0 | NIGHT | DAY |
99 | LAO | ERROR STATUS | 0 | – | 1 | 0 | – | – |
Notes:
•Points not listed are not used in this application.
•All points have the same value for English units and SI units.
59