13.7.7 | Special Control Parameters |
|
|
| ||||
|
|
|
|
|
|
|
|
|
Parameter |
| Function / Title | Bank | Mask |
| Adjustment Range |
| Multiplier |
|
|
|
|
|
|
|
|
|
0069 | 0 / 1 | FFFF | 0000 | ∼ 03E8 (0.00 ∼ 10.00) |
| 0.01 | ||
006A ∼ |
| Reserved | | |
| |
| |
006F |
|
|
| |||||
|
|
|
|
|
|
|
| |
0070 | END FREQUENCY | 0 / 1 | FFFF | 0000 | ∼ 0BB8 (0.00 ∼ 30.00) |
| 0.01 | |
0071 | RUN FREQUENCY | 0 / 1 | FFFF | 0000 | ∼ Fmax |
| 0.01 | |
0072 | RUN FREQUENCY | 0 / 1 | FFFF | 0000 | ∼ 0BB8 (0.00 ∼ 30.00) |
| 0.01 | |
| HYSTERESIS |
|
|
|
|
|
| |
0073 | ENABLE JUMP | 0 / 1 | 0080 | 0000: Function OFF | (0) | | ||
| FREQUENCIES |
|
| 0080: Function ON | (1) |
| ||
0074 |
| JUMP FREQUENCY #1 | 0 / 1 | FFFF | 0000 | ∼ Fmax |
| 0.01 |
0075 |
| JUMP FREQUENCY #1 | 0 / 1 | FFFF | 0000 | ∼ 0BB8 (0.00 ∼ 30.00) |
| 0.01 |
|
| BANDWIDTH |
|
|
|
|
|
|
0076 | 1 | JUMP FREQUENCY #2 | 0 / 1 | FFFF | 0000 | ∼ Fmax |
| 0.01 |
0077 | JUMP FREQUENCY #2 | 0 / 1 | FFFF | 0000 | ∼ 0BB8 (0.00 ∼ 30.00) |
| 0.01 | |
|
| BANDWIDTH |
|
|
|
|
|
|
0078 |
| JUMP FREQUENCY #3 | 0 / 1 | FFFF | 0000 | ∼ Fmax |
| 0.01 |
0079 |
| JUMP FREQUENCY #3 | 0 / 1 | FFFF | 0000 | ∼ 0BB8 (0.00 ∼ 30.00) |
| 0.01 |
|
| BANDWIDTH |
|
|
|
|
|
|
007A ∼ |
| Reserved | | |
| |
| |
007F |
|
|
| |||||
|
|
|
|
|
|
|
| |
0080 | PWM CARRIER FREQUENCY | 0 / 1 | 00FF | 0005 | ∼ 0064 (0.5 ∼ 10.0) |
| 0.1 | |
| (Note 1) |
|
|
|
|
|
| |
Note 1: Actual adjustment range depends on inverter rating. |
|
|
|
| ||||
75