Parameter

 

Function / Title

Bank

Mask

 

Adjustment Range

 

Multiplier

 

 

 

 

 

 

 

 

0133

STALL PROTECTION

0 / 1

0040

0000: ON

(0)

 

ENABLE

 

 

0040: OFF

(1)

 

0134

0

STALL

0 / 1

00FF

000A 00D7 (10 215)

 

1

 

PROTECTION

 

 

 

 

 

 

 

 

CURRENT LEVEL

 

 

 

 

 

 

0135

 

UNDERVOLTAGE TRIP

0 / 1

0080

0000: Trip disabled

(0)

 

SELECTION

 

 

0080: Trip (during run)

(1)

 

0136

UNDERVOLTAGE DETECT

0 / 1

FFFF

0000 03E8 (0.00 10.00)

 

0.01

 

TIME

 

 

 

 

 

 

0137

LOW CURRENT DETECT

0 / 1

0008

0000: Trip disabled

(0)

 

SELECTION

 

 

0008: Trip on detection

(1)

 

0138

LOW CURRENT DETECT

0 / 1

00FF

0000 0064 (0 100)

 

1

 

LEVEL

 

 

 

 

 

 

0139

LOW CURRENT

0 / 1

00FF

0000 00FF (0 255)

 

1

 

DETECTION TIME

 

 

 

 

 

 

0140

OUTPUT SHORT-

0 / 1

0003

0000:

Standard motor

(0)

 

CIRCUIT DETECTION

 

 

0001:

High-speed motor

(1)

 

 

SELECT

 

 

0002:

Positioning use (standard

 

 

 

 

 

 

 

 

motor)

(2)

 

 

 

 

 

 

0003: Positioning use (high-speed

 

 

 

 

 

 

 

 

motor)

(3)

 

0141

OVERTORQUE TRIP

0 / 1

0040

0000: Trip disabled

(0)

 

SELECTION

 

 

0040: Trip enabled

(1)

 

0142

OVERTORQUE TRIP

0 / 1

00FF

0000 00C8 (0 200)

 

1

 

LEVEL

 

 

 

 

 

 

0143

FAULT TRIP EEPROM

0 / 1

0002

0000:

Data cleared when powered

 

 

SAVE ENABLE

 

 

 

OFF

(0)

 

 

 

 

 

 

0002: Data retained when powered

 

 

 

 

 

 

 

 

OFF

(1)

 

0144

COOLING FAN CONTROL

0 / 1

0004

0000:

Automatic (temperature

 

 

SELECTION

 

 

 

detection)

(0)

 

 

 

 

 

 

0004:

Always ON

(1)

 

0145

CUMULATIVE RUN

0 / 1

FFFF

0000 C34B (0.00 999.90)

 

0.02

 

TIMER ALARM SETTING

 

 

 

 

 

 

80