Parameter |
| Function / Title | Bank | Mask |
| Adjustment Range |
| Multiplier |
|
|
|
|
|
|
|
| |
0133 | STALL PROTECTION | 0 / 1 | 0040 | 0000: ON | (0) | | ||
| ENABLE |
|
| 0040: OFF | (1) |
| ||
0134 | 0 | STALL | 0 / 1 | 00FF | 000A ∼ 00D7 (10 ∼ 215) |
| 1 | |
| PROTECTION |
|
|
|
|
|
| |
|
| CURRENT LEVEL |
|
|
|
|
|
|
0135 |
| UNDERVOLTAGE TRIP | 0 / 1 | 0080 | 0000: Trip disabled | (0) | | |
| SELECTION |
|
| 0080: Trip (during run) | (1) |
| ||
0136 | UNDERVOLTAGE DETECT | 0 / 1 | FFFF | 0000 ∼ 03E8 (0.00 ∼ 10.00) |
| 0.01 | ||
| TIME |
|
|
|
|
|
| |
0137 | LOW CURRENT DETECT | 0 / 1 | 0008 | 0000: Trip disabled | (0) | | ||
| SELECTION |
|
| 0008: Trip on detection | (1) |
| ||
0138 | LOW CURRENT DETECT | 0 / 1 | 00FF | 0000 ∼ 0064 (0 ∼ 100) |
| 1 | ||
| LEVEL |
|
|
|
|
|
| |
0139 | LOW CURRENT | 0 / 1 | 00FF | 0000 ∼ 00FF (0 ∼ 255) |
| 1 | ||
| DETECTION TIME |
|
|
|
|
|
| |
0140 | OUTPUT SHORT- | 0 / 1 | 0003 | 0000: | Standard motor | (0) | | |
| CIRCUIT DETECTION |
|
| 0001: | (1) |
| ||
| SELECT |
|
| 0002: | Positioning use (standard |
|
| |
|
|
|
|
|
| motor) | (2) |
|
|
|
|
|
| 0003: Positioning use |
|
| |
|
|
|
|
|
| motor) | (3) |
|
0141 | OVERTORQUE TRIP | 0 / 1 | 0040 | 0000: Trip disabled | (0) | | ||
| SELECTION |
|
| 0040: Trip enabled | (1) |
| ||
0142 | OVERTORQUE TRIP | 0 / 1 | 00FF | 0000 ∼ 00C8 (0 ∼ 200) |
| 1 | ||
| LEVEL |
|
|
|
|
|
| |
0143 | FAULT TRIP EEPROM | 0 / 1 | 0002 | 0000: | Data cleared when powered |
| | |
| SAVE ENABLE |
|
|
| OFF | (0) |
| |
|
|
|
|
| 0002: Data retained when powered |
|
| |
|
|
|
|
|
| OFF | (1) |
|
0144 | COOLING FAN CONTROL | 0 / 1 | 0004 | 0000: | Automatic (temperature |
| | |
| SELECTION |
|
|
| detection) | (0) |
| |
|
|
|
|
| 0004: | Always ON | (1) |
|
0145 | CUMULATIVE RUN | 0 / 1 | FFFF | 0000 ∼ C34B (0.00 ∼ 999.90) |
| 0.02 | ||
| TIMER ALARM SETTING |
|
|
|
|
|
|
80