13.6.3 Subpoint Details

This section gives a brief overview of each subpoint, including any notable behavior or settings. Further information may be obtained by referring to applicable Mitsubishi ASD documentation.

1. ADDRESS

This is the FLN address of the drive. It can be changed via FLN or via the gateway’s serial console.

2. APPLICATION

This is the Application ID for FLN on the A500/F700 drives. This ID is assigned by Siemens for each unique application, and correlates directly to a particular point list approved at the time of release. The Application ID assigned to the A500/F700 drives is 2750.

3. FREQ OUTPUT

The output frequency of the drive in Hertz. Corresponds to drive parameter 1003.

4. OUTPUT CUR

The output current of the drive in Amps. Corresponds to drive parameter 1004.

5. OUTPUT VOLT

The output voltage of the drive in Volts. Corresponds to drive parameter 1005.

6. SPECIAL MON

This is the point which allows monitoring of a selected special monitor item. The meaning of the value, scaling and engineering units displayed here depends on the setting of the MON SELECT item (point #7). Corresponds to drive parameter 1006.

7. MON SELECT

This point allows a selection of data codes to be written to it. Each designated code corresponds to a particular drive status item that will then be reflected in the SPECIAL MON item (point #6). Please refer to the applicable Mitsubishi documentation for a list of available codes. Corresponds to drive parameter 1007.

8. ACCEL TIME

Acceleration time in seconds. Corresponds to drive parameter 7.

9. DECEL TIME

Deceleration time in seconds. Corresponds to drive parameter 8.

10. CMD FWD.STOP

Commands the drive to run forward or stop. Note that commanding this point is effective only when the drive is configured for network start/stop control. Corresponds to drive command parameter 1014, bit #1.